2013-04-06 11:59:15 | 515 NORTH FLAGLER DRIVE - SUITE #1800 |
| PERMIT #13030512 |
| REVIEW COMMENTS - FIRE DEPARTMENT |
| |
| REVIEW #2: FAIL COMMENT |
| (1) RESPONSE COMMENT: FOR ISSUANCE OF A GENERAL |
| BUILDING PERMIT, SECTION 105.3.1.2(2) OF THE FLORIDA |
| BUILDING CODE REQUIRES SEALED FIRE PROTECTION |
| CONSTRUCTION DOCUMENTS FOR THE DESIGN OR ALTERATION OF |
| 50 OR MORE AUTOMATIC FIRE SPRINKLERS. AFTER THE |
| BUILDING PERMIT HAS BEEN ISSUED, THE SUBCONTRACTORS CAN |
| THEN SUBMIT SHOP DRAWINGS (CONFORMING TO THE ENGINEERED |
| CONSTRUCTION DOCUMENTS) FOR A SUB-PERMIT. |
| REPEAT COMMENT - ORIGINAL COMMENT: FOR ISSUANCE OF A |
| GENERAL BUILDING PERMIT, SECTION 105.3.1.2(2) OF THE |
| FLORIDA BUILDING CODE REQUIRES SEALED FIRE PROTECTION |
| CONSTRUCTION DOCUMENTS FOR THE DESIGN OR ALTERATION OF |
| 50 OR MORE AUTOMATIC FIRE SPRINKLERS. PER FLORIDA |
| ADMINISTRATIVE CODE SECTION 61G15-32.004, FIRE |
| PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE |
| POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF |
| APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT, |
| CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR |
| AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER |
| SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA) |
| AND ANY PERFORMANCE BASED INFORMATION SUCH AS |
| PRE-ENGINEERED SYSTEMS. |
| |
| REVIEW #2: PROVISO/NON-FAIL COMMENTS: |
| (2) REPEAT COMMENT: PROVIDE DRAWING NOTE INDICATING ALL |
| CONSTRUCTION AND DEMOLITION WORK SHALL CONFORM TO THE |
| REQUIREMENTS OF NFPA 241. TRASH AND CONSTRUCTION DEBRIS |
| SHALL BE REMOVED FROM THE SITE DAILY. ALL DEMOLITION |
| AND CONSTRUCTION AREAS SHALL HAVE "NO SMOKING" SIGNS |
| POSTED. |
| |
| (3) REPEAT COMMENT: PROVIDE DRAWING NOTE INDICATING |
| FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING |
| DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A |
| FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN |
| 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE |
| PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST |
| BE SUBMITTED IN WRITING (FAX: 561-804-4774) AND |
| APPROVED BY THE OFFICE OF THE FIRE MARSHAL LOCATED AT |
| 500 NORTH DIXIE HIGHWAY. |
| |
| REVIEW #2: NEW COMMENT |
| (4) SHEET E-2: HOLD-OPEN DOORS (NEW ELEVATOR LOBBY |
| DOORS) REQUIRE THE AUTOMATIC RELEASING MECHANISM IS |
| ACTIVATED BY THE OPERATION OF APPROVED SMOKE DETECTORS |
| LISTED FOR DOOR LEAF RELEASE SERVICE PER NFPA 72. |
| |