2013-03-27 14:54:12 | 13030510 |
| 213 SEVILLE ROAD |
| SFD INTERIOR RENOVATION |
| |
| PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING |
| ELECTRICAL REVIEW COMMENTS. THE SCOPE OF ELECTRICAL |
| WORK PROPOSED IS NOT EXACTLY CLEAR. |
| |
| IS THE ELECTRICAL SERVICE NEW OR EXISTING? |
| |
| SHOW LOCATION OF ELECTRICAL PANEL BOARDS AND |
| DISCONNECTS WITH SAFETY CLEARANCES. NEC 110.26, 215.5 |
| |
| AN INTERSYSTEM BONDING STRIP IS REQUIRED AT THE MAIN |
| SERVICE GROUND. NEC 250.94 |
| |
| REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO |
| INCLUDE INTERCONNECTED SMOKE ALARMS BOTH WITHIN AND |
| OUTSIDE EACH SLEEPING AREA. IF THE RESIDENCE HAS GAS |
| APPLIANCES, AN ATTACHED GARAGE OR A FIRE PLACE A CARBON |
| MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET OF EACH |
| ROOM USED FOR SLEEPING. 2010 FBC R314, 315 |
| |
| NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11 |
| |
| ARC FAULT CIRCUIT PROTECTION IS REQUIRED FOR ALL NEW |
| GENERAL PURPOSE OUTLETS INCLUDING LIGHTING. NEC 210.12 |
| |
| THE BATHROOM REQUIRES A DEDICATED 20 AMP BRANCH |
| CIRCUIT. NEC 210.11 (C) (3) |
| |
| A GFCI PROTECTED RECEPTACLE IS REQUIRED OUTSIDE AT THE |
| FRONT AND BACK ENTRANCE AREA. NEC 210.52 (E) (1) |
| |
| GFCI PROTECTION IS REQUIRED FOR ALL RECEPTACLES LOCATED |
| IN THE STUDIO/CABANA. NEC 210.8 |
| |
| SHOW THE KITCHEN COUNTER TOP RECEPTACLES TO BE GFCI |
| PROTECTED. NEC 210.8 |
| |
| RECEPTACLES ARE REQUIRED SO THAT AT NO POINT ALONG THE |
| FLOOR IN ANY WALL IS MORE THAN 6 FEET FROM A RECEPTACLE |
| OUTLET AND AT WALL SPACES 2 FEET OR MORE IN WIDTH. NEC |
| 210.52 |
| |
| PROVIDE A GROUND ROD AND GROUNDING ELECTRODE FOR THE |
| STUDIO/CABANA ELECTRIC PANEL BOARD. NEC 250.32 |
| |
| |
| ROBERT LECKY |
| ELECTRICAL PLANS EXAMINER |