Plan Review Notes
Plan Review Notes For Permit 13030510
Permit Number 13030510
Review Stop E
Sequence Number 1
Notes
Date Text
2013-03-27 14:54:1213030510
 213 SEVILLE ROAD
 SFD INTERIOR RENOVATION
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 ELECTRICAL REVIEW COMMENTS. THE SCOPE OF ELECTRICAL
 WORK PROPOSED IS NOT EXACTLY CLEAR.
  
 IS THE ELECTRICAL SERVICE NEW OR EXISTING?
  
 SHOW LOCATION OF ELECTRICAL PANEL BOARDS AND
 DISCONNECTS WITH SAFETY CLEARANCES. NEC 110.26, 215.5
  
 AN INTERSYSTEM BONDING STRIP IS REQUIRED AT THE MAIN
 SERVICE GROUND. NEC 250.94
  
 REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO
 INCLUDE INTERCONNECTED SMOKE ALARMS BOTH WITHIN AND
 OUTSIDE EACH SLEEPING AREA. IF THE RESIDENCE HAS GAS
 APPLIANCES, AN ATTACHED GARAGE OR A FIRE PLACE A CARBON
 MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET OF EACH
 ROOM USED FOR SLEEPING. 2010 FBC R314, 315
  
 NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11
  
 ARC FAULT CIRCUIT PROTECTION IS REQUIRED FOR ALL NEW
 GENERAL PURPOSE OUTLETS INCLUDING LIGHTING. NEC 210.12
  
 THE BATHROOM REQUIRES A DEDICATED 20 AMP BRANCH
 CIRCUIT. NEC 210.11 (C) (3)
  
 A GFCI PROTECTED RECEPTACLE IS REQUIRED OUTSIDE AT THE
 FRONT AND BACK ENTRANCE AREA. NEC 210.52 (E) (1)
  
 GFCI PROTECTION IS REQUIRED FOR ALL RECEPTACLES LOCATED
 IN THE STUDIO/CABANA. NEC 210.8
  
 SHOW THE KITCHEN COUNTER TOP RECEPTACLES TO BE GFCI
 PROTECTED. NEC 210.8
  
 RECEPTACLES ARE REQUIRED SO THAT AT NO POINT ALONG THE
 FLOOR IN ANY WALL IS MORE THAN 6 FEET FROM A RECEPTACLE
 OUTLET AND AT WALL SPACES 2 FEET OR MORE IN WIDTH. NEC
 210.52
  
 PROVIDE A GROUND ROD AND GROUNDING ELECTRODE FOR THE
 STUDIO/CABANA ELECTRIC PANEL BOARD. NEC 250.32
  
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6718
  