2013-04-02 14:09:5113030468
 501 FERN ST #C
 SHELL CONSTRUCTION FOR FUTURE TENANTS
  
 THE RESPONSE SUBMITTED FOR 2ND REVIEW IS NOT AS EARLIER
 DISCUSSED. THE SUGGESTION WAS TO PROVIDE A TEMPORARY
 ELECTRIC SERVICE TO BEGIN CONSTRUCTION PENDING A FOLLOW
 UP SUBMITTAL WHICH ADDRESSES THE NEC CODE REQUIREMENT
 FOR A SINGLE POINT OF SERVICE. THE PLANS STILL SHOW
 MULTIPLE ELECTRICAL SERVICES.
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS.
  
 THE ELECTRICAL SERVICE MAINS MUST BE GROUPED IN ONE
 LOCATION. YOUR REQUEST FOR MULTIPLE SERVICE POINTS HAS
 BEEN DENIED. THIS STRUCTURE IS NOT SUFFICIENTLY LARGE
 NOR DOES IT EXHIBIT ANY SPECIAL CONDITIONS WHICH WOULD
 WARRANT THE SPECIAL PERMISSION REQUESTED FOR MULTIPLE
 ELECTRICAL SERVICES. THE PRINCIPAL SAFETY RULE FOR
 ELECTRICAL SERVICES REQUIRES A BUILDING OR STRUCTURE TO
 HAVE ONE POINT OF SERVICE. NEC 230.2, 230.71, 230.72
  
 AN INTERSYSTEM BONDING STRIP IS REQUIRED AT THE MAIN
 SERVICE GROUND. NEC 250.94
  