2013-03-29 10:54:02PLANS DENIED
 1) PROVIDE A DETAIL ON THE PLANS ON HOW RTU 1,2,3 AND 4
 ARE TIED DOWN TO THE CURB. PER SECTION 301.12
 WIND RESISTANCE 2010 FBC (M)
 2) SHOW DUCT DETECTORS ON THE ALARM AND MECHANICAL
 PLANS
 FOR RTU 1,2,3 AND 4. PER SECTION 606.2.1 SUPPLY AIR
 SYSTEMS
 AND 606.4.1 SUPERVISION.
 3) PROVIDE WELDERS CERTIFICATION TO THE CITY BEFOR
 WELDING STARTS ON THE JOB