Plan Review Notes For Permit 13030468 |
Permit Number |
13030468 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2013-03-29 10:54:02 | PLANS DENIED | | 1) PROVIDE A DETAIL ON THE PLANS ON HOW RTU 1,2,3 AND 4 | | ARE TIED DOWN TO THE CURB. PER SECTION 301.12 | | WIND RESISTANCE 2010 FBC (M) | | 2) SHOW DUCT DETECTORS ON THE ALARM AND MECHANICAL | | PLANS | | FOR RTU 1,2,3 AND 4. PER SECTION 606.2.1 SUPPLY AIR | | SYSTEMS | | AND 606.4.1 SUPERVISION. | | 3) PROVIDE WELDERS CERTIFICATION TO THE CITY BEFOR | | WELDING STARTS ON THE JOB | | PLAN REVIEW BY HAROLD MOSER | | [email protected] | | OFFICE 561-805-6732 | | FAX 561-805-6676 | | | | |
|