Plan Review Notes For Permit 13030468 |
Permit Number |
13030468 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2013-03-26 16:03:59 | 13030468 | | 501 FERN ST #C | | SHELL CONSTRUCTION FOR FUTURE TENANTS | | | | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING | | REVIEW COMMENTS. | | | | THE ELECTRICAL SERVICE MAINS MUST BE GROUPED IN ONE | | LOCATION. YOUR REQUEST FOR MULTIPLE SERVICE POINTS HAS | | BEEN DENIED. THIS STRUCTURE IS NOT SUFFICIENTLY LARGE | | NOR DOES IT EXHIBIT ANY SPECIAL CONDITIONS WHICH WOULD | | WARRANT THE SPECIAL PERMISSION REQUESTED FOR MULTIPLE | | ELECTRICAL SERVICES. THE PRINCIPAL SAFETY RULE FOR | | ELECTRICAL SERVICES REQUIRES A BUILDING OR STRUCTURE TO | | HAVE ONE POINT OF SERVICE. NEC 230.2, 230.71, 230.72 | | | | AN INTERSYSTEM BONDING STRIP IS REQUIRED AT THE MAIN | | SERVICE GROUND. NEC 250.94 | | | | ROBERT LECKY | | ELECTRICAL PLANS EXAMINER | | [email protected] | | 561-805-6718 | | |
|