Plan Review Notes
Plan Review Notes For Permit 13030406
Permit Number 13030406
Review Stop Z
Sequence Number 2
Notes
Date Text
2013-05-30 16:10:24FAILED
  
 PLEASE PROVIDE RESPONSES TO THE COMMENTS IN WRITING.
  
 1) REPEAT COMMENT: THERE IS NEW EQUIPMENT BEING
 INSTALLED ON THE ROOF. IN ACCORDANCE WITH THE CITYPLACE
 DRI, PLEASE PROVIDE VERIFICATION THAT ALL ROOFTOP
 MECHANICAL EQUIPMENT, INCLUDING BUT NOT LIMITED TO SUCH
 ITEMS AS PUBLIC AND PRIVATE UTILITY SERVICE
 CONNECTIONS; HEATING, VENTILATING, AND AIR CONDITIONING
 SYSTEMS; COMMUNICATIONS DEVICES; AND RELATED EQUIPMENT,
 SHALL BE SCREENED FROM PUBLIC VIEW THROUGH ANY
 COMBINATION OF LANDSCAPING, WALLS AND EQUIPMENT
 LOCATION. PROVIDE VERIFICATION OF THE SCREENING. ADDING
 THE 7 FEET PLUS IN HEIGHT A/C AND CURB TO THE SECTION
 DRAWINGS DOES NOT SHOW THAT THE EQUIPMENT IS SCREENED
 FROM PUBLIC VIEW, SPECIFICALLY FROM THE OKEECHOBEE
 BOULEVARD RIGHT-OF-WAY.
  
 PLEASE CONTACT ERIC SCHNEIDER @ (561) 822-1446.
  
  