Plan Review Notes For Permit 13030378 |
Permit Number |
13030378 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2013-03-21 11:32:26 | FBC 2010 PLUMBING REVIEW #1 | | | | 1. THE WATER CLOSETS IN ROOMS # 220, 223, 224, & 257 | | ARE NOT VENTED PER P-909 WET VENTING. | | A. ROOM 257 & 220 THE SINKS ARE REQUIRED TO CONNECT | | DOWNSTREAM OF THE RESTROOM WET VENT. | | B. ROOM 224 THE WATER CLOSET IS NOT VENTED. | | C. ROOM 223 THE MOP SINK IS REQUIRED TO CONNECT | | DOWNSTREAM OF THE RESTROOM WET VENT. | | | | 909.1 HORIZONTAL WET VENT PERMITTED. | | ANY COMBINATION OF FIXTURES WITHIN TWO BATHROOM GROUPS | | LOCATED ON THE SAME FLOOR LEVEL IS PERMITTED TO BE | | VENTED BY A HORIZONTAL WET VENT. THE WET VENT SHALL BE | | CONSIDERED THE VENT FOR THE FIXTURES AND SHALL EXTEND | | FROM THE CONNECTION OF THE DRY VENT ALONG THE DIRECTION | | OF THE FLOW IN THE DRAIN PIPE TO THE MOST DOWNSTREAM | | FIXTURE DRAIN CONNECTION TO THE HORIZONTAL BRANCH | | DRAIN. EACH WET-VENTED FIXTURE DRAIN SHALL CONNECT | | INDEPENDENTLY TO THE HORIZONTAL WET VENT. ONLY THE | | FIXTURES WITHIN THE BATHROOM GROUPS SHALL CONNECT TO | | THE WET-VENTED HORIZONTAL BRANCH DRAIN. ANY ADDITIONAL | | FIXTURES SHALL DISCHARGE DOWNSTREAM OF THE HORIZONTAL | | WET VENT. | | | | REVIEW BY | | LARRY WAGNER | | CHIEF PLUMBING INSPECTOR | | PHONE # 805-6692 | | EMAIL [email protected] | | FAX # 805-6676 | | |
|