Plan Review Notes
Plan Review Notes For Permit 13030378
Permit Number 13030378
Review Stop M
Sequence Number 1
Notes
Date Text
2013-03-28 13:17:48PLANS DENIED
 DUCT THAT PENETRATE ELECTRICAL ROOM
 # 225 REQUIRE FIRE DAMPERS. PER SECTION 607.5.1 FIRE
 WALLS
 PLAN REVIEW BY HAROLD MOSER