2013-03-15 12:41:30 | 13030378 | | 770 NORTH POINT PKWY #200 | | MEDICAL OFFICE INTERIOR | | | | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING | | REVIEW COMMENT. | | | | WIRING IN ALL PATIENT CARE AREAS / EXAM ROOMS REQUIRES | | A SPECIFIC LISTED WIRING METHOD THAT PROVIDES REDUNDANT | | GROUNDING AND INCLUDES AN INSULATED COPPER EQUIPMENT | | GROUND. NEC 517.13 | | | | ROBERT LECKY | | ELECTRICAL PLANS EXAMINER | | [email protected] | | 561-805-6718 | | |
|