Plan Review Notes For Permit 13030376 |
Permit Number |
13030376 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2013-05-21 16:00:25 | MECHANICAL PROVISO: | | 2010 FBC-ENERGY CONSERVATION 503.2.5.4 SHUTOFF DAMPER | | CONTROLS. | | BOTH OUTDOOR AIR SUPPLY AND EXHAUST DUCTS SHALL BE | | EQUIPPED WITH DAMPERS | | THAT WILL AUTOMATICALLY SHUT WHEN THE SYSTEMS OR SPACES | | SERVED ARE NOT IN USE. | | VENTILATION OUTSIDE AIR DAMPERS SHALL BE CAPABLE OF | | AUTOMATICALLY SHUTTING OFF | | DURING PREOCCUPANCY BUILDING WARMUP, COOLDOWN, AND | | SETBACK, EXCEPT WHEN | | VENTILATION REDUCES ENERGY COSTS (E.G., NIGHT PURGE) OR | | WHEN VENTILATION MUST | | BE SUPPLIED TO MEET CODE REQUIREMENTS. | | | | JAMES A. WITMER CBO | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | TEL: 561-805-6715 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | |
|