2013-05-21 16:00:25MECHANICAL PROVISO:
 2010 FBC-ENERGY CONSERVATION 503.2.5.4 SHUTOFF DAMPER
 CONTROLS.
 BOTH OUTDOOR AIR SUPPLY AND EXHAUST DUCTS SHALL BE
 EQUIPPED WITH DAMPERS
 THAT WILL AUTOMATICALLY SHUT WHEN THE SYSTEMS OR SPACES
 SERVED ARE NOT IN USE.
 VENTILATION OUTSIDE AIR DAMPERS SHALL BE CAPABLE OF
 AUTOMATICALLY SHUTTING OFF
 DURING PREOCCUPANCY BUILDING WARMUP, COOLDOWN, AND
 SETBACK, EXCEPT WHEN
 VENTILATION REDUCES ENERGY COSTS (E.G., NIGHT PURGE) OR
 WHEN VENTILATION MUST
 BE SUPPLIED TO MEET CODE REQUIREMENTS.
  