2013-05-18 17:04:31 | 1 HARVARD CIRCLE - SECOND FLOOR |
| PERMIT #13030376 |
| REVIEW COMMENTS - FIRE DEPARTMENT |
| |
| *****PROVISO***** |
| |
| RESPONSE: PER NFPA 101 SECTION 6.1.14.1.2, WHERE EXIT |
| ACCESS FROM AN OCCUPANCY TRAVERSES ANOTHER OCCUPANCY, |
| THE MULTIPLE OCCUPANCY SHALL BE TREATED AS A MIXED |
| OCCUPANCY. FOR MIXED USE OCCUPANCIES, THE MOST |
| STRINGENT FIRE AND LIFE SAFETY REQUIREMENTS OF EACH |
| OCCUPANCY SHALL APPLY. BECAUSE THE ASSEMBLY SPACES MUST |
| USE THE BUSINESS OCCUPANCY EGRESS ROUTES AND ENTIRE |
| TENANT SPACE HAS AN OCCUPANT LOAD EXCEEDING 100 PERSONS |
| SO DOOR #100A AND #100B REQUIRE PANIC HARDWARE. |
| |
| ORIGINAL COMMENT: FOR ASSEMBLY OCCUPANCIES WITH AN |
| OCCUPANT LOAD OF 100 OR MORE PERSONS, PANIC HARDWARE |
| SHALL BE PROVIDED ON DOORS TO RELEASE THE LOCK/LATCH. |
| NO OTHER LOCKS OR LATCHES ARE PERMITTED THAT WOULD NOT |
| BE RELEASED BY THE PANIC HARDWARE. AS A SUBSTITUTE FOR |
| PANIC HARDWARE, THE MAIN ENTRANCE IS PERMITTED TO HAVE |
| AN INTERIOR KEYED DOOR LOCK (AND NO LATCH) WITH A |
| READILY VISIBLE SIGN STATING THIS DOOR TO REMAIN |
| UNLOCKED WHEN THE BUILDING IS OCCUPIED. SIGN LETTERS |
| SHALL BE AT LEAST 1 INCH IN HEIGHT. A THUMB TURN STYLE |
| LOCK IS NOT PERMITTED TO BE SUBSTITUTED FOR A KEYED |
| LOCK. |
| |