Plan Review Notes
Plan Review Notes For Permit 13030332
Permit Number 13030332
Review Stop B
Sequence Number 2
Notes
Date Text
2013-04-03 17:16:33****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 FROM PREVIOUS LIST:
  
 1. REVISE PLAN TO INCLUDE ALL STRUCTURAL DETAILS
 REQUIRED FOR INSPECTIONS AND TO SHOW RESISTANCE TO WIND
 LOADS FBC R 301. FOR INSTANCE: ENGINEER'S SPECIFICATION
 FOR FOOTING (CONTRACTOR'S PLAN PROPOSES FOOTER,
 ENGINEER'S DETAIL SHOWS "EXISTING SLAB" BUT NO MINIMUM
 DIMENSIONS OTHER THAN EDGE DISTANCE), GIRT TO POST,
 DOOR JAMB TO SLAB, 1X2 TO HOST, CABLE TO CORNER.
  
 2. PLAN IS NOT ENTIERELY LEGIBLE. PLEASE PROVIDE
 LEGIBLE PLANS, FBC 107.
  
 2ND REVIEW, THE SITE SPECIFIC WAS REVISED BUT NOT THE
 SCREEN ENCLOSURE DETAIL PLAN.
  
 CONTRACTOR CALLED, LEFT MESSAGE - EITHER REVISE PLAN TO
 INCLUDE ALL PERTINENT STRUCTURAL DETAILS OR CALL ME TO
 DISCUSS.
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved