Plan Review Notes For Permit 13030332 |
Permit Number |
13030332 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2013-03-20 09:11:39 | ****CORRECTIONS**** | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | FBC FLORIDA BUILDING CODE 2010 | | FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL | | | | 1. REVISE PLAN TO INCLUDE ALL STRUCTURAL DETAILS | | REQUIRED FOR INSPECTIONS AND TO SHOW RESISTANCE TO WIND | | LOADS FBC R 301. FOR INSTANCE: ENGINEER'S SPECIFICATION | | FOR FOOTING (CONTRACTOR'S PLAN PROPOSES FOOTER, | | ENGINEER'S DETAIL SHOWS "EXISTING SLAB" BUT NO MINIMUM | | DIMENSIONS OTHER THAN EDGE DISTANCE), GIRT TO POST, | | DOOR JAMB TO SLAB, 1X2 TO HOST, CABLE TO CORNER. | | | | 2. PLAN IS NOT ENTIERELY LEGIBLE. PLEASE PROVIDE | | LEGIBLE PLANS, FBC 107. | | |
|