2013-03-12 18:05:07****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. PRODUCT APPROVALS TO BE REVIEWED BY DESIGNER OF
 RECORD.
  
 2. EITHER DESIGNER OF RECORD IS TO SPECIFY DESIGN
 PRESSURES OR THE FBC/ASCE7-10 TABLE WILL BE USED TO
 DETERMINE DESIGN PRESSURES. IN ORDER TO DO THIS, PLEASE
 PROVIDE ROOF PITCH, MEAN ROOF HEIGHT.
  
 3. TWO DIFFERENT DESIGN PRESSURES ARE HIGHLIGHTED.
 PLEASE INDICATE FASTENING PROPOSED FOR ZONES 1, 2, AND
 3.
  
 4. PLEASE BE ADVISED THAT THIS REVIEW HAS BEEN DONE
 WITH 30# FELT AS THE UNDERLAYMENT. ANY OTHER
 UNDERLAYMENTS WILL REQUIRE A REVISION AS THIS STRUCTURE
 HAS AN ICYNENE INSULATION SYSTEM (ADVISORY ONLY).
  
  