 REVIEW COMMENTS - FIRE DEPARTMENT
  
 *****PROVISO - SUBMIT REVISION*****
  
 THE EXTERIOR STUCCO OVERHANG NEEDS TO BE PROTECTED BY
 THE AUTOMATIC SPRINKLER SYSTEM. CONFIRM PROTECTION IS
 EXISTING OR WILL BE INSTALLED.
  
 THE TRION AIR PURIFICATION SYSTEM ("AIR BOSS KES"
 SERIES) CLEANING, WASHING AND MAINTENANCE SCHEDULE
 SHALL BE INDICATED ON THE ENGINEER'S DRAWINGS FOR
 PERMAMENT PUBLIC RECORD PURPOSES. FOR EXAMPLE, "TRION
 RECOMMENDS STARTING WITH A MANUAL
 WASHING FREQUENCY OF AT LEAST ONCE A WEEK. DAILY MANUAL
 WASHING IS NOT UNUSUAL FOR UNITS OPERATING ON HEAVY
 KITCHEN EXHAUST HOODS OR SIMILAR CONTAMINANTS." ALSO,
 "FIRE SUPPRESSION SYSTEM ? EVERY 6 MONTHS: PROPERLY
 TRAINED AND QUALIFIED PERSONNEL SHALL COMPLETE
 INSPECTION, CLEANING AND SERVICING OF THE FIRE
 SUPPRESSION SYSTEM." THESE ARE JUST SOME OF THE
 REQUIREMENTS; CHECK THE INSTALLATION MANAUL FOR OTHER
 SPECIFICS.
  