Plan Review Notes For Permit 13030265 |
Permit Number |
13030265 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2013-03-12 14:50:22 | 610 CLEMATIS STREET | | PERMIT #13030265 | | MASTER #13030263 | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | *****PROVISO - SUBMIT REVISION***** | | | | THE EXTERIOR STUCCO OVERHANG NEEDS TO BE PROTECTED BY | | THE AUTOMATIC SPRINKLER SYSTEM. CONFIRM PROTECTION IS | | EXISTING OR WILL BE INSTALLED. | | | | THE TRION AIR PURIFICATION SYSTEM ("AIR BOSS KES" | | SERIES) CLEANING, WASHING AND MAINTENANCE SCHEDULE | | SHALL BE INDICATED ON THE ENGINEER'S DRAWINGS FOR | | PERMAMENT PUBLIC RECORD PURPOSES. FOR EXAMPLE, "TRION | | RECOMMENDS STARTING WITH A MANUAL | | WASHING FREQUENCY OF AT LEAST ONCE A WEEK. DAILY MANUAL | | WASHING IS NOT UNUSUAL FOR UNITS OPERATING ON HEAVY | | KITCHEN EXHAUST HOODS OR SIMILAR CONTAMINANTS." ALSO, | | "FIRE SUPPRESSION SYSTEM ? EVERY 6 MONTHS: PROPERLY | | TRAINED AND QUALIFIED PERSONNEL SHALL COMPLETE | | INSPECTION, CLEANING AND SERVICING OF THE FIRE | | SUPPRESSION SYSTEM." THESE ARE JUST SOME OF THE | | REQUIREMENTS; CHECK THE INSTALLATION MANAUL FOR OTHER | | SPECIFICS. | | | | WESLEY JOLIN | | FIRE INVESTIGATOR & INSPECTOR | | OFFICE OF THE FIRE MARSHAL | | WEST PALM BEACH FIRE RESCUE | | [email protected] | | (561) 805-6730 | | |
|