Plan Review Notes
Plan Review Notes For Permit 13030262
Permit Number 13030262
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2013-03-21 13:12:45610 CLEMATIS STREET
 MASTER #13030262
 (HOOD PERMIT #13030265)
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY
 RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING
 NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM
 WWW.KNOXBOX.COM.
  
 EVERY ASSEMBLY OCCUPANCY ROOM NOT HAVING FIXED SEATS
 SHALL HAVE THE OCCUPANT LOAD OF THE ROOM POSTED IN A
 CONSPICUOUS PLACE NEAR THE MAIN EXIT FROM THE ROOM.
 SIGNS SHALL BE DURABLE AND INDICATE THE NUMBER OF
 OCCUPANTS PERMITTED FOR EACH ROOM.
  
 PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH
 EXIT SIGNS.
  
 THE EXTERIOR STUCCO OVERHANG NEEDS TO BE PROTECTED BY
 THE AUTOMATIC SPRINKLER SYSTEM. CONFIRM PROTECTION IS
 EXISTING OR WILL BE INSTALLED.
  
 THE TRION AIR PURIFICATION SYSTEM ("AIR BOSS KES"
 SERIES) CLEANING, WASHING AND MAINTENANCE SCHEDULE
 SHALL BE INDICATED ON THE ENGINEER'S DRAWINGS FOR
 PERMAMENT PUBLIC RECORD PURPOSES. FOR EXAMPLE, "TRION
 RECOMMENDS STARTING WITH A MANUAL
 WASHING FREQUENCY OF AT LEAST ONCE A WEEK. DAILY MANUAL
 WASHING IS NOT UNUSUAL FOR UNITS OPERATING ON HEAVY
 KITCHEN EXHAUST HOODS OR SIMILAR CONTAMINANTS." ALSO,
 "FIRE SUPPRESSION SYSTEM: EVERY 6 MONTHS: PROPERLY
 TRAINED AND QUALIFIED PERSONNEL SHALL COMPLETE
 INSPECTION, CLEANING AND SERVICING OF THE FIRE
 SUPPRESSION SYSTEM." THESE ARE JUST SOME OF THE
 REQUIREMENTS; CHECK THE INSTALLATION MANAUL FOR OTHER
 SPECIFICS.
  