2013-03-11 13:53:34 | 425 24TH STREET | | PERMIT #13030228 | | MASTER #12030294 | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | THE ADDRESS PROVIDED ON THE PLANS (425 24TH STREET) | | DOES NOT MATCH THE ADDRESS (2401 SPRUCE AVENUE) | | PROVIDED ON THE PERMIT APPLICATION. | | | | THE CORRIDORS AND HALLWAYS APPEAR TO HAVE AN | | INSUFFICIENT NUMBER OF NOTIFICATION APPLIANCES. | | DISTANCES BETWEEN SOME DEVICES IS OVER 100 FEET. | | DISTANCES BETWEEN SOME DEVICES AND END OF CORRIDOR IS | | OVER 56 FEET. | | | | THE PLANS INDICATE A CANDELA OF 100 CD FOR SEVERAL | | APPLIANCES; HOWEVER, THE EQUIPMENT CUTSHEETS DO NOT | | INDICATE 100 CANDELA AS BEING A SELECTABLE OPTION. | | | | STUDIO #1-#3, THE COMPUTER LAB AND THE MEN'S/WOMEN'S | | RESTROOMS INDICATE "PHASE 2 AND PHASE 3." THESE SPACES | | WILL NOT BE ABLE TO BE UTILIZED IN PHASE 1 UNLESS THE | | FIRE ALARM SYSTEM IS DESIGNED TO INCORPORATE THESE | | AREAS. | | | | WESLEY JOLIN | | FIRE INVESTIGATOR & INSPECTOR | | OFFICE OF THE FIRE MARSHAL | | WEST PALM BEACH FIRE RESCUE | | [email protected] | | (561) 805-6730 | | |
|