Plan Review Notes
Plan Review Notes For Permit 13030120
Permit Number 13030120
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2013-03-11 09:11:552015 OKEECHOBEE BOULEVARD
 PERMIT #13030120
 MASTER #12120635
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 THERE SHALL BE NO SHUTOFF VALVE DOWNSTREAM OF THE FIRE
 DEPARTMENT CONNECTION. CONNECT FDC ABOVE RISER
 BUTTERFLY VALVE OR ELIMINATE RISER CONTROL VALVE AND
 PROVIDE PERMANENT WEATHERPROOF SIGNAGE INDICATING THE
 BACKFLOW PREVENTER IS THE SHUTOFF FOR THE SPRINKLER
 SYSTEM.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  