Date Text
2013-04-01 10:58:125720 PREMIER PARK DRIVE
 PERMIT #13030119
 MASTER #12120739
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 VAULT ROOM WALLS SHALL BE FULL HEIGHT TO THE UNDERSIDE
 OF THE ROOF DECK TO CREATE NON-COMBUSTIBLE CONCEALED
 SPACE OTHERWISE SPRINKLER PROTECTION WILL BE NEEDED TO
 PROTECT/COOL THE ROOF STRUCTURE.
  