2013-03-11 10:59:415720 PREMIER PARK DRIVE
 PERMIT #13030119
 MASTER #12120739
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 NO PREACTION SYSTEM EQUIPMENT INFORMATION SUBMITTED AND
 NEITHER THE SPRINKLER SHOP DRAWINGS NOR FIRE ALARM SHOP
 DRAWINGS (PERMIT #13030226) SHOW THE DETECTION DEVICES
 TO BE USED WITH THE DOUBLE-INTERLOCK PREACTION SYSTEM
 PROTECTING THE VAULT AND SERVER ROOM.
  
 ESFR SPRINKLERS HAVE BEEN DELETED ABOVE THE NORTH
 PORTION OF OPEN AREA #112. THERE ALSO 5 BRANCHLINES
 THAT ARE NOT CONNECTED TO THE GRID SYSTEM AT EITHER THE
 NORTH OR SOUTH END.
  
 DESIGN AREA #4 INDICATES A REDUCED HYDRAULIC AREA FOR
 UTILIZING QUICK-RESPONSE SPRINKLERS; HOWEVER, THE 155F
 (TEMPERATURE) TYCO EC-8 RECESSED PENDENT SPRINKLER IS
 STANDARD RESPONSE ACCORDING TO TABLE B IN THE CUT
 SHEETS.
  
 FOR SYSTEM PRESSURES EXCEEDING 100 PSI, ARMOVERS AND
 END OF BRANCH LINE PENDENT SPRINKLERS SHALL BE
 PROTECTED FROM UPWARD MOVEMENT. HANGERS SHALL BE
 LOCATED WITHIN 12-INCHES OF THE DROP ELBOW. INDICATE
 THE HANGER TYPE OR METHOD TO BE USED FOR RESTRAINING
 UPWARD MOVEMENT.
  
 PROVIDE A FLEXIBLE DROP DETAIL INDICATING THE MAXIMUM
 NUMBER OF BENDS PERMITTED AND THE MINIMUM BEND RADIUS
 PERMITTED IN THE LISTING DATA.
  
 SUBMIT PRODUCT DATA FOR THE FLEXIBLE SPRINKLER DROPS
 PROPOSED TO BE INSTALLED. INDICATE IF THE DROPS ARE
 BRAIDED OR UNBRAIDED.
  
 INDICATE THE MAXIMUM LENGTH OF FLEXIBLE DROP TO BE
 USED.
  