2013-03-05 12:55:58****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. INDICATE WHICH APPROVED ASSEMBLY IS PROPOSED.
  
 2. PROVIDE BUILDING HEIGHT SO DESIGN PRESSURES CAN BE
 DETERMINED, FBC R 301.
  
 3. IF THE BUILDING HAS A MEAN ROOF HEIGHT OF 15', WORST
 CASE DESIGN PRESSURE IS -95.7. THE ASSEMBLIES ON PAGES
 22 AND 23 OF THE NOA MEET THIS PRESSURE. IF ANOTHER
 ASSEMBLY IS PROPOSED, PLEASE PROVIDE CALCULATIONS FOR
 THE ENHANCED FASTENING, SEE GENERAL LIMITATION #7 ON
 THE LAST PAGE OF THE NOA. CALCULATIONS ARE TO BE
 PREPARED BY AN ARCHITECT, ENGINEER, OR REGISTERED ROOF
 CONSULTANT PER NOA LIMITATIONS. FBC R 301.
  
 4. VALUE HAS BEEN ADJUSTED PER MARSHALL & SWIFT, FBC
 109.
  
 5. PROVIDE A PLAN SHOWING WHICH PORTION OF THE ROOF IS
 TO BE REPLACED.
  
  
  