Plan Review Notes
Plan Review Notes For Permit 13030088
Permit Number 13030088
Review Stop B
Sequence Number 2
Notes
Date Text
2013-09-14 11:54:31****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 FROM PREVIOUS LIST:
  
 FBC R 301, RESISTANCE TO WIND LOADS:
  
 1. ROOF FRAMING DRAWING DOES NOT APPEAR TO BE DRAWN
 CORRECTLY, PLEASE REVISE. IT SHOWS A MANSARD SECTION
 BEYOND THE ENCLOSURE.
  
 RESPONSE INDICATES THAT THIS IS NOT A MANSARD. SEE FBC
 107. PROVIDE A PLAN VIEW AND ELEVATIONS. THE PLANS
 SUBMITTED ARE 3D. CONSTRUCTION DRAWINGS DO NOT
 TYPICALLY INCLUDE THIS TYPE OF DETAIL. IF A SURVEY WAS
 INCLUDED, THAT MAY HAVE ADDRESSED THIS ISSUE.
  
 2. SPANS NOT CLEAR; PROVIDE PANEL SPANS FOR FRONT
 ELEVATION. ROOF BEAMS APPEAR TO BE UNDERSIZED. IT
 APPEARS THAT THE 8' WALL HEIGHT TABLE WAS USED, BUT
 WALL HEIGHT IS SHOWN AS 115".
  
 NOT ADDRESSED.
  
 3. SEE NOTE ON SHEET 2, BEAM SPAN CALCULATION NOTE,
 SPANS ARE BASED ON HOST STRUCTURE MOUNTING POINT AND
 WALL HEIGHT BEING THE SAME MEASUREMENT.
  
 NOT ADDRESSED.
  
 4. PROVIDE A SURVEY WHICH SHOWS LOCATION OF PROPOSED
 SCREEN ENCLOSURE IN RELATION TO THE PROPERTY LINE FBC R
 302.
  
 NOT ADDRESSED.
  
 5. THE FLOOR PLAN IS NOT CLEAR, NOT CONSISTENT WITH THE
 SCREEN SITE SPECIFIC AND DOES NOT INCLUDE ANY
 DIMENSIONS. PLEASE REVISE.
  
 NOT ADDRESSED.
  
 WHEN RESUBMITTING, INCLUDE A DETAILED RESPONSE LETTER.
  