2013-06-29 07:52:00 | ****CORRECTIONS**** |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 [email protected] |
| FBC FLORIDA BUILDING CODE 2010 |
| FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL |
| |
| FROM PREVIOUS LIST: |
| |
| 1-2. OK |
| |
| 3. BEDROOM #1 DOES NOT EMERGENCY MEANS OF ESCAPE AND |
| RESCUE WHICH COMPLIES WITH FBC R 310. IT APPEARS THAT |
| THIS WAS CONVERTED FROM A PORCH TO A BEDROOM WITHOUT A |
| PERMIT. PROVIDE AN EGRESS OPENING. |
| |
| 2ND REVIEW - WINDOW SIZE INCREASED BUT NO DETAIL |
| PROVIDED FOR NEW ENLARGED OPENING, FBC 109, FBC 2010 |
| RESIDENTIAL 301. |
| |
| 4. OK |
| |
| 5. PROVIDE A STRUCTURAL DETAIL FOR THE INFILL FBC R |
| 301, FBC 107. |
| |
| NOT ADDRESSED. |
| |
| 6. OK |
| |
| 7. AS IT APPEARS THAT UNINHABITABLE SPACE WAS CONVERTED |
| TO HABITABLE SPACE, IMPACT FEE ASSESSMENT REQUIRED. |
| CONTACT 561-233-5025 FOR MORE INFORMATION. REVISE PLAN |
| TO REFLECT CONVERSION OF PORCH TO LIVING SPACE WITH |
| APPLICABLE DETAILS. |
| |
| NEW COMMENTS: |
| |
| 8. SHUTTER PRODUCT APPROVALS SUBMITTED ON 2ND REVIEW. |
| COMPLETE THE SAMPLE INSTALLATION SCHEDULE OR PROVIDE |
| ALL INFORMATION TO SHOW CODE COMPLIANCE IN ANOTHER |
| FORMAT, FBC*106, FBC R301, FBC1609. TWO SETS REQUIRED. |
| THIS FORM IS AVAILABLE IN THE LOBBY OR ON THE INTERNET |
| AT |
| HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/PDF/SCHEDULE_FOR_ |
| INSTALLATION.PDF |
| |
| 9. CONTRACTOR INFORMED THAT NO MECHANICAL WORK IS |
| PROPOSED, ALL EXISTING. THERE IS NO RECORD OF AIR |
| CONDITIONING INSTALLED AT THIS LOCATION. PLEASE |
| ADDRESS. FBC 107 |
| |
| |
| |