Plan Review Notes For Permit 13020828 |
Permit Number |
13020828 |
|
Review Stop |
G |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2013-05-10 16:39:22 | 2010 FBC | | | | DENIED | | | | 1) THE PLANS SPECIFY THE LONGEST LENGTH AS 80 FEET WITH | | A TOTAL DEMAND OF 320,000 BTUS AND 3/4" DIAMETER | | SCHEDULE 40 PIPE METALLIC PIPE. FBC FUEL GAS TABLE | | 402.4(2) FOR 12" WC AND 0.5" PRESSURE DROP SHOWS THAT | | 80 FEET OF 3/4" PIPE HAS A CAPACITY OF 117,000 BTU | | WHICH IS NOT ENOUGH. PLEASE REVISE THE GAS PLAN. | | | | 2) THE GAS ISOMETRIC DRAWING APPEARS TO SHOW A 1/2" | | PIPE COMING FROM THE GAS METER AND THEN CHANGING TO | | 3/4" PIPE. SEE GAS PIPE SIZING TABLE 402.4(2). | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|