2013-03-22 16:46:522010 FBC
  
 FUEL GAS DENIED
  
 1) THE GAS INPUT IN BTUS SHOWN ON THE GAS PLAN ARE
 INCORRECT. THE SPECIFICATIONS THAT WERE SUBMITTED FOR
 THE TANKLESS WATER-HEATER REQUIRES A GAS INPUT OF
 180,000 BTUS. ACCORDING TO FBCR TABLE G2413.2 (402),
 THE RANGE IS 65,000 BTUS, THE CLOTHES DRYER IS 35,000
 BTUS AND THE TOTAL BTUS SHOULD BE 320,000 BTUS. PLEASE
 CORRECT.
  
 2) THE 1/2" PIPE SIZE IS TOO SMALL FOR THE GAS LOAD FOR
 SCHEDULE 40 METALLIC PIPE WITH A 11" W.C. AND 0.5 P.D.
 AND A LENGTH OF 80'. SEE TABLE G2413.4(1) [402.4(2)]
 AND G2413.4.1 (402.4.1).
  
 3) UPDATE THE REFERENCED CODE TO THE 2010 FUEL GAS
 CODE. FBCR CHAPTER 43
  