Plan Review Notes For Permit 13020828 |
Permit Number |
13020828 |
|
Review Stop |
G |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2013-03-22 16:46:52 | 2010 FBC | | | | FUEL GAS DENIED | | | | 1) THE GAS INPUT IN BTUS SHOWN ON THE GAS PLAN ARE | | INCORRECT. THE SPECIFICATIONS THAT WERE SUBMITTED FOR | | THE TANKLESS WATER-HEATER REQUIRES A GAS INPUT OF | | 180,000 BTUS. ACCORDING TO FBCR TABLE G2413.2 (402), | | THE RANGE IS 65,000 BTUS, THE CLOTHES DRYER IS 35,000 | | BTUS AND THE TOTAL BTUS SHOULD BE 320,000 BTUS. PLEASE | | CORRECT. | | | | 2) THE 1/2" PIPE SIZE IS TOO SMALL FOR THE GAS LOAD FOR | | SCHEDULE 40 METALLIC PIPE WITH A 11" W.C. AND 0.5 P.D. | | AND A LENGTH OF 80'. SEE TABLE G2413.4(1) [402.4(2)] | | AND G2413.4.1 (402.4.1). | | | | 3) UPDATE THE REFERENCED CODE TO THE 2010 FUEL GAS | | CODE. FBCR CHAPTER 43 | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|