2013-03-18 16:23:26 | 13020828 |
| 317 PALMETTO STREET |
| INTERIOR REMODEL |
| |
| THE ELECTRICAL PLAN IS INSUFFICIENTLY DETAILED TO |
| APPROVE. PLEASE PROVIDE THE FOLLOWING. |
| |
| SHOW SIZE AND LOCATION OF THE ELECTRICAL SERVICE AND |
| PANEL. PROVIDE A PANEL SCHEDULE SHOWING NEW AND |
| EXISTING LOADS. SHOW EXISTING AND NEW OUTLETS. NEC |
| 215.5 |
| |
| REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO |
| INCLUDE INTERCONNECTED SMOKE ALARMS BOTH WITHIN AND |
| OUTSIDE EACH SLEEPING AREA. IF THE RESIDENCE HAS GAS |
| APPLIANCES, AN ATTACHED GARAGE OR A FIRE PLACE A CARBON |
| MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET OF EACH |
| ROOM USED FOR SLEEPING. 2010 FBC R314, 315 |
| |
| PROVIDE GFCI PROTECTED OUTLETS IN THE BATHROOMS. NEC |
| 210.52 |
| |
| A GFCI PROTECTED RECEPTACLE IS REQUIRED OUTSIDE IN |
| FRONT AND AT THE BACK OF THE RESIDENCE. NEC 210.70 |
| |
| ALL GENERAL PURPOSE OUTLETS INCLUDING THOSE IN THE |
| BEDROOMS AND SMOKE ALARMS MUST BE AFCI PROTECTED. NEC |
| 210.12 |
| |
| SHOW KITCHEN CIRCUITS WITH GFCI PROTECTION NEC 210.8, |
| 210.52 |
| |
| NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11 |
| |
| PROVIDE ONE 20 AMP LAUNDRY CIRCUIT. NEC 210.11 (C) (2) |
| |
| PROVIDE A MINIMUM OF TWO 20 AMP KITCHEN CIRCUITS. NEC |
| 210.11 (C)(1) |
| |
| PROVIDE A BRANCH CIRCUIT TO THE BATHROOMS. NEC 210.11 |
| (C)(3) |
| |
| PROVIDE AN INTER SYSTEM BONDING STRIP AT ELECTRIC |
| SERVICE. NEC 250.94 |
| |
| AT LEAST ONE WALL SWITCHED-CONTROLLED LIGHTING OUTLET |
| SHALL BE INSTALLED IN EVERY HABITABLE ROOM. NEC 210.70 |
| |
| RECEPTACLES SHALL BE SPACED SO THAT AT NO POINT ALONG |
| THE FLOOR IN ANY WALL IS MORE THAN 6 FEET FROM A |
| RECEPTACLE OUTLET. NEC 210.52 (A) (2) |
| |
| ADDITIONAL RECEPTACLES ARE REQUIRED FOR ANY WALL SPACE |
| MORE THAN 2 FEET IN WIDTH. NEC 10.52 (A) (2) |
| |
| |
| ROBERT LECKY |
| ELECTRICAL PLANS EXAMINER |