2013-03-14 14:25:31 | BUILDING PLAN REVIEW |
| PERMIT: 130206667 |
| ADD: 3260 S DIXIE HWY BLDG # 3, LOTS 12-18 |
| CONT: L&M HOMEBUILDERS, INC |
| TEL: (561)436-0668 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: 3/14/2013 |
| ACTION: DENIED |
| |
| 1) ) MISSING FROM THE TITLE BLOCK IS THE ADDRESS FOR |
| THIS BUILDING # 3.107.2.1.4 WEST PALM BCH |
| ADMINISTRATIVE CODE 2010. 107.2.1.4 QUALITY OF BUILDING |
| PLANS. THE BUILDING OFFICIAL MAY ESTABLISH THROUGH |
| DEPARTMENTAL POLICY, OTHER STANDARDS FOR PLANS AND |
| SPECIFICATIONS, IN ORDER TO PROVIDE CONFORMITY TO ITS |
| RECORD RETENTION PROGRAM. THIS POLICY MAY INCLUDE SUCH |
| THINGS AS MINIMUM SIZE, SHAPE, CONTRAST, CLARITY, OR |
| OTHER ITEMS RELATED TO RECORDS MANAGEMENT. |
| |
| 2) THE DISCREPANCY IN THE TYPE OF OCCUPANCY THAT WILL |
| OCCUR. THE COVER SHEET INDICATES THE BUILDING OCCUPANCY |
| TO BE A R2 WHERE AS THE 81/8X 11 SHEET INDICATING THE |
| TYPE OF FIRE SPRINKLERS TO BE INSTALLED AS A TOWNHOUSE |
| TYPE OF OCCUPANCY A R3, THE STRUCTURAL SHEET ALSO LIST |
| THIS OCCUPANCY AS A R3. THE SURVEYS FOR UNITS 12- 18 DO |
| INCLUDE A 18.5 FT SPACE AT THE REAR OF THE BUILDING TO |
| THE PROPERTY LINE MAKING IT APPEAR THESE UNITS ARE TO |
| BE FEE SIMPLE TOWNHOUSE CONSTRUCTION. THIS REVIEW WILL |
| BE TREATED AS TOWNHOUSE R-3 OCCUPANCY. |
| |
| F S 553.73 |
| 2010 FBC-R CHAPTER 2 |
| DEFINITIONS |
| |
| TOWNHOUSE. A SINGLE-FAMILY DWELLING UNIT CONSTRUCTED IN |
| A GROUP OF THREE OR MORE ATTACHED UNITS WITH PROPERTY |
| LINES SEPARATING EACH UNIT IN WHICH EACH UNIT EXTENDS |
| FROM FOUNDATION TO ROOF AND WITH A YARD OR PUBLIC WAY |
| ON AT LEAST TWO SIDES. |
| |
| PUBLIC WAY. A STREET, ALLEY OR OTHER PARCEL OF LAND |
| OPEN TO THE OUTSIDE AIR LEADING TO A STREET, THAT HAS |
| BEEN DEEDED, DEDICATED OR OTHERWISE PERMANENTLY |
| APPROPRIATED TO THE PUBLIC FOR PUBLIC USE AND WHICH HAS |
| A CLEAR WIDTH AND HEIGHT OF NOT LESS THAN 10 FEET (3048 |
| MM). |
| |
| |
| ARCHITECTURAL BOARD |
| |
| ?481.203DEFINITIONS.?AS USED IN THIS PART: |
| |
| ?(7)?TOWNHOUSE? IS A SINGLE-FAMILY DWELLING UNIT NOT |
| EXCEEDING THREE STORIES IN HEIGHT WHICH IS CONSTRUCTED |
| IN A SERIES OR GROUP OF ATTACHED UNITS WITH PROPERTY |
| LINES SEPARATING SUCH UNITS. EACH TOWNHOUSE SHALL BE |
| CONSIDERED A SEPARATE BUILDING AND SHALL BE SEPARATED |
| FROM ADJOINING TOWNHOUSES BY THE USE OF SEPARATE |
| EXTERIOR WALLS MEETING THE REQUIREMENTS FOR ZERO |
| CLEARANCE FROM PROPERTY LINES AS REQUIRED BY THE TYPE |
| OF CONSTRUCTION AND FIRE PROTECTION REQUIREMENTS; OR |
| SHALL BE SEPARATED BY A PARTY WALL; OR MAY BE SEPARATED |
| BY A SINGLE WALL MEETING THE FOLLOWING REQUIREMENTS: |
| ?(A)SUCH WALL SHALL PROVIDE NOT LESS THAN 2 HOURS OF |
| FIRE RESISTANCE. PLUMBING, PIPING, DUCTS, OR ELECTRICAL |
| OR OTHER BUILDING SERVICES SHALL NOT BE INSTALLED |
| WITHIN OR THROUGH THE 2-HOUR WALL UNLESS SUCH MATERIALS |
| AND METHODS OF PENETRATION HAVE BEEN TESTED IN |
| ACCORDANCE WITH THE STANDARD BUILDING CODE. |
| ?(B)SUCH WALL SHALL EXTEND FROM THE FOUNDATION TO THE |
| UNDERSIDE OF THE ROOF SHEATHING, AND THE UNDERSIDE OF |
| THE ROOF SHALL HAVE AT LEAST 1 HOUR OF FIRE RESISTANCE |
| FOR A WIDTH NOT LESS THAN 4 FEET ON EACH SIDE OF THE |
| WALL. |
| ?C)EACH DWELLING UNIT SHARING SUCH WALL SHALL BE |
| DESIGNED AND CONSTRUCTED TO MAINTAIN ITS STRUCTURAL |
| INTEGRITY INDEPENDENT OF THE UNIT ON THE OPPOSITE SIDE |
| OF THE WALL. |
| |
| |
| |
| 3) THE COVER SHEET DOE INDICATE THIS BUILDING WILL BE |
| FIRE SPPRINKLERED BUT NO FIRE SPRINKLER PLANS HAVE BEEN |
| PROVIDED. PLEASE REVIEW THE 2010 FBC-B 903.2.8 & |
| 903.2.11.3.1. |
| |
| 2D) THE FLOOR PLAN A-1UA IS REVERSED TO THE SURVEY, IS |
| THERE GOING TO BE A REVERSE FLOOR PLAN FOR LAY OUT AND |
| CONFIGURATIONS THAT MAY BE DIFFERENT THAN SHOWN? |
| 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED. |
| |
| 3) SHEET A-1.1 THE DOOR SCHEDULE LIST DOOR # 2 & 21 AS |
| A "C" LABELED DOOR, PLEASE REFER TO COVERSHEET UNDER |
| TBUILDING ELEMENTS INDICATES A "C" LABEL 45 MINUTE |
| DOOR. PLEASE REFER TO THE 2010 FBC-R 302.5.1. |
| |
| 4) SHEET A1.1 INDICATES ADATABLE UNITS FOR FAIR |
| HOUSING, THE FRONT ENTRY INDICATES A ZERO DIFFERENCE IN |
| GRADE BUT THERE IS A DISCREPANCY WITH THE STRUCTURAL |
| S-1 INDICATING A 4" CHANGE IN GRADE? SEE FAIR HOUSING. |
| PRIMARY ENTRY DOORS. ANSI 4.13. |
| |
| 5) SHEET A-5 INDICATES TWO WALL SECTIONS BETWEEN THE |
| MANGO TYPE UNIT AND SKY UNITS BUT THE DETAIL DOES NOT |
| SPELL OUT WHERE THIS DETAIL IS LOCATED. SHEET A-9 |
| PROVIDES WALL CUT SECTIONS AT LOT LINES BUT THE DETAIL |
| BETWEEN THESE UNITS. PLEASE PROVIDE COMPLIANCE WITH |
| 2010 FBC-R 302.2.1 CONTINUNITY. THE PLANS ALSO DO NOT |
| PROVIDE WHAT TYPE OF SOFFIT MATERIAL WILL BE IN THIS |
| AREA, IF THERE IS SOFFIT VENTS? |
| |
| 6) ATTIC ACCESS 2010 FBC-R 807.1 SHEET A1.5 SKY UNITS |
| APPEAR TO HAVE ATTIC ACCESS IN FRONT OF WASH ROOM # 3 |
| BUT NOT LABELED, SHEETS A1-7 & A1-8 DO NOT INDICATE |
| ATTIC ACCESS AT ALL. |
| |
| 7) THE ROOFING PRODUCT APPROVAL ENTEGRA ESTATE S NOA |
| 11-051.02 DOES NOT INDICATE WHICH TYPE OF FASTENING |
| SYSTEM WILL BE USED ON THIS INSTALATION PLEASE CIRCLE |
| THE TYPE OF SYSTEM TO BE USED. NOTE IS A FOAM ON OR |
| MORTAR SYSTEM IS TO BE USED PLEASE PROVIDE THE PRODUCT |
| APPROVALS FOR THIS TYPE OF APPLICATION. 2010 FBC-R |
| R905.3 & R905.3.7. |
| |
| 8) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| INFORMATION. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| CONSTRUCTION SERVICES HOME PAGE |
| HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| |
| PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| |
| MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| |
| |