2013-05-20 09:55:136300 SOUTH DIXIE HIGHWAY - SUITES 101 & 102
 PERMIT #13020613
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 REPEAT COMMENT (X2): PROVIDE TACTILE SIGNAGE AT ALL
 REQUIRED EXIT DOORS WITH EXIT SIGNS.
  
 REPEAT COMMENT (X2): DOORS SERVING AN OCCUPANT LOAD OF
 50 OR MORE PERSONS SHALL SWING IN THE DIRECTION OF
 EGRESS.
  
 REPEAT COMMENT (X1): SHEET A-1 INDICATES AN EXERCISE
 AREA OF 490 SQ.FT.; HOWEVER, THE SCALED MEASUREMENT
 INDICATES AN AREA OF 800 SQ.FT. (25 FT. X 32 FT.).
 USING AN OCCUPANT LOAD FACTOR OF 15 SQ.FT. PER PERSON
 (EXERCISE ROOM WITHOUT EQUIPMENT PER TABLE 7.3.1.2 NFPA
 101) RESULTS IN AN OCCUPANT LOAD OF 54 PERSONS.THE FIRE
 CODE DEFINES AN ASSEMBLY OCCUPANCY AS AN OCCUPANCY USED
 FOR THE GATHERING OF 50 OR MORE PERSONS FOR
 DELIBERATION, WORSHIP, ENTERTAINMENT, EATING, DRINKING
 OR SIMILAR USAGE.
  
 REPEAT COMMENT (X1): EVERY ASSEMBLY OCCUPANCY ROOM NOT
 HAVING FIXED SEATS SHALL HAVE THE OCCUPANT LOAD OF THE
 ROOM POSTED IN A CONSPICUOUS PLACE NEAR THE MAIN EXIT
 FROM THE ROOM. SIGNS SHALL BE DURABLE AND INDICATE THE
 NUMBER OF OCCUPANTS PERMITTED FOR EACH ROOM.
  
 REPEAT COMMENT (X1): SHEET A-1, A 1-HOUR FIRE-RATED
 CEILING BARRIER IS NEEDED FOR THE STORAGE/WATER HEATER
 AREA LOCATED BENEATH THE CONCRETE STAIRS.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730