2013-05-20 09:55:13 | 6300 SOUTH DIXIE HIGHWAY - SUITES 101 & 102 |
| PERMIT #13020613 |
| REVIEW COMMENTS - FIRE DEPARTMENT |
| |
| REPEAT COMMENT (X2): PROVIDE TACTILE SIGNAGE AT ALL |
| REQUIRED EXIT DOORS WITH EXIT SIGNS. |
| |
| REPEAT COMMENT (X2): DOORS SERVING AN OCCUPANT LOAD OF |
| 50 OR MORE PERSONS SHALL SWING IN THE DIRECTION OF |
| EGRESS. |
| |
| REPEAT COMMENT (X1): SHEET A-1 INDICATES AN EXERCISE |
| AREA OF 490 SQ.FT.; HOWEVER, THE SCALED MEASUREMENT |
| INDICATES AN AREA OF 800 SQ.FT. (25 FT. X 32 FT.). |
| USING AN OCCUPANT LOAD FACTOR OF 15 SQ.FT. PER PERSON |
| (EXERCISE ROOM WITHOUT EQUIPMENT PER TABLE 7.3.1.2 NFPA |
| 101) RESULTS IN AN OCCUPANT LOAD OF 54 PERSONS.THE FIRE |
| CODE DEFINES AN ASSEMBLY OCCUPANCY AS AN OCCUPANCY USED |
| FOR THE GATHERING OF 50 OR MORE PERSONS FOR |
| DELIBERATION, WORSHIP, ENTERTAINMENT, EATING, DRINKING |
| OR SIMILAR USAGE. |
| |
| REPEAT COMMENT (X1): EVERY ASSEMBLY OCCUPANCY ROOM NOT |
| HAVING FIXED SEATS SHALL HAVE THE OCCUPANT LOAD OF THE |
| ROOM POSTED IN A CONSPICUOUS PLACE NEAR THE MAIN EXIT |
| FROM THE ROOM. SIGNS SHALL BE DURABLE AND INDICATE THE |
| NUMBER OF OCCUPANTS PERMITTED FOR EACH ROOM. |
| |
| REPEAT COMMENT (X1): SHEET A-1, A 1-HOUR FIRE-RATED |
| CEILING BARRIER IS NEEDED FOR THE STORAGE/WATER HEATER |
| AREA LOCATED BENEATH THE CONCRETE STAIRS. |
| |