2013-05-20 07:39:28 | BUILDING PLAN REVIEW |
| PERMIT: 13020613 |
| ADD: 6300 S DIXIE HWY |
| CONT: ATLANTIDA |
| TEL: (561)313-8126 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 3RD REVIEW |
| DATE: 04/20/2013 |
| ACTION: DENIED |
| |
| ***** NOTE*****FLORIDA STATUTE 553.80(2)(B) |
| DESIGN PROFESSIONAL DOCUMENTS. |
| WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS' |
| DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN |
| ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING |
| CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS |
| REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO |
| CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY |
| NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, |
| EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY, |
| ACCESSIBILITY,LIGHTING, VENTILATION, MECHANICAL, |
| PLUMBING, AND GAS SYSTEMS, OR OTHER REQUIREMENTS |
| IDENTIFIED BY RULE OF THE FLORIDA BUILDING COMMISSION |
| ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL GOVERNMENT |
| SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH REVIEW THE |
| PLANS ARE REJECTED FOR THAT CODE VIOLATION A FEE OF |
| FOUR TIMES THE AMOUNT OF THE PORTION OF THE PERMIT FEE |
| ATTRIBUTED TO PLAN REVIEW. |
| |
| 1-2) COMPLIED. |
| |
| |
| 3) 3RD REQUEST, SEMI-COMPLIED. SHEET A-1 NOTE # 4 |
| INDICATES A BUSINESS OCCUPANCY AND THE REFERENECE TO |
| CODE SECTION 306 WHICH IS FACTORY? THEN UNDER THE |
| HEADING NOTES OCCUPANCY TYPE ; ASSEMBLY, THIS IS A YOGA |
| STUDIO, THIS TRUELY APPEARS TO BE A EXERCISE ROOM |
| WITHOUT EQUIPMENT AND THE 15 SQ FT PER PERSON SHOULD BE |
| USED PROVIDE WHAT AREA WILL BE USED FOR YOGA PROVIDE |
| THE SQ FT PER AREA AND OCCUPANT LOADS FOR EACH AREA. |
| THE YOGA AREA AREA IS 490 SQ FT / 15 SQ FT PER OCCUPANT |
| = 33 OCCUPANTS. . PLEASE PROVIDE WHAT METHOD YOU USED |
| TO PROVIDE AN OCCUPANT LOAD OF 15. 2010 FBC-B TABLE |
| 1004.1.1. THE BUILDING OFFICIAL AND FIRE MARSHALL BOTH |
| AGREE THAT YOGA MATS DO NOT CONSTITUTE GYM EQUIPMENT |
| AND THE 50 SQ FT CAN NOT BE TAKEN FOR ALLOWABLE SQUARE |
| FEET PER OCCUPANT FOR GYM EQUIPMENT. |
| |
| 4)3RD REQUEST. SHEET 1-A UNDER NOTES CLASSIFIES THIS |
| BUILDING AS A TYPE 5 BUILDING. UNDER THE 2010 FBC-B |
| TABLE 503.1 & TABLE 601 THE TABLES LIST 5A OR 5B. |
| |
| 5-7) COMPLIED. |
| NEW COMMENTS: |
| |
| 8)COMPLIED. |
| |
| 9) 2ND REQUEST. THE PLANS ALSO SHOW FOR THE SECOND TIME |
| A EXIT FROM THE SECOND STORY BUT THE DETAIL A -A-1 |
| INDICATES A ROOF ABOVE, PLEASE CLARIFY WHAT TYPE |
| CONDITION IS LOCATED ABOVE THIS UNIT? IS THERE ANOTHER |
| OCCUPANCY TYPE ABOVE AND HOW ARE YOU OBTAINING |
| OCCUPANCY SEPERATION FROM THE UNIT ABOVE? 2010 FBC-B |
| TABLE 508.4. |
| |
| 10) 2ND REQUEST. SHEET A1 WITH THE STAIRWELL FROM THE |
| SECOND FLOOR, IT APPEARS THAT YOU CAN ENTER THE TENANT |
| SPACE THROUGH A BUILDING UTILITY CLOSET, WHERE IS THE |
| TENANT SEPERATION LINE, AND WHY CAN YOU ENTER THE |
| UTILITY CLOSET FROM THE VERTICAL EXIT. THE 2010 FBC-B |
| 1022.4 OPENINGS THROUGH AN EXIT ENCLOSURE ARE |
| PROHIBITED EXCEPT FOR REQUIRED EXIT DOORS.1022.3 |
| OPENINGS IN EXIT ENCLOSURES OTHER THAN UNPROTECTED |
| EXTERIOR OPENINGS SHALL BE LIMITED TO THOSE NECESSARY |
| FOR EXIT ACCESS TO THE ENCLOSURE FROM NORMALLY OCCUPIED |
| SPACES AND FOR EGRESS FROM THE ENCLOSURE. |
| |
| 11)2ND REQUEST. BOTH THE NEW A1 SHEET AS WELL AS THE LS |
| SHEET INDICATE A WATER HEATER IN THE VERTICAL EXIT |
| ENCLOSURE. 2010 FBC-B 1022.4 PENETRATIONS. |
| PENETRATIONS INTO AND OPENINGS THROUGH AN EXIT |
| ENCLOSURE ARE PROHIBITED EXCEPT FOR REQUIRED EXIT |
| DOORS, EQUIPMENT AND DUCTWORK NECESSARY FOR INDEPENDENT |
| VENTILATION OR PRESSURIZATION, SPRINKLER PIPING, |
| STANDPIPES, ELECTRICAL RACEWAY FOR FIRE DEPARTMENT |
| COMMUNICATION SYSTEMS AND ELECTRICAL RACEWAY SERVING |
| THE EXIT ENCLOSURE AND TERMINATING AT A STEEL BOX NOT |
| EXCEEDING 16 SQUARE INCHES (0.010 M2). SUCH |
| PENETRATIONS SHALL BE PROTECTED IN ACCORDANCE WITH |
| SECTION 713. THERE SHALL BE NO PENETRATIONS OR |
| COMMUNICATION OPENINGS, WHETHER PROTECTED OR NOT, |
| BETWEEN ADJACENT EXIT ENCLOSURES. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| CONSTRUCTION SERVICES HOME PAGE |
| HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| |
| PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| |
| MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |