2013-04-09 08:51:08FBC 2010 EXISTING BUILDING CODE
 FBC 2010 ACCESSIBILITY CODE
 FBC 2010 PLUMBING REVIEW #1
 DENIED:
  
 PLUMBING REVIEW IS PENDING THE OUTCOME FOR THE
 OCCUPANCY TYPE AND
 OCCUPANT LOAD. PLEASE SEE BUILDING REVIEW COMMENTS.
  
 A BUSINESS OCCUPANCY WITH LESS THAN 3000 SQUARE FEET
 WOULD ONLY REQUIRE ONE RESTROOM, AND WITH 15 OR LESS
 OCCUPANTS WOULD NOT REQUIRE A HI/LOW DRINKING FOUNTAIN
 (FBC
 ACCESSIBILITY CODE 211.2)
 FBC PLUMBING TABLE 403.1
  
 ALSO, A YOGA STUDIO COULD BE AN ASSEMBLY OCCUPANCY.
 THEN
 SEPARATE FACILITIES ARE REQUIRED FOR EACH SEX, A HI/LOW
 DRINKING FOUNTAIN (IF OCCUPANT LOAD IS OVER 15), AND A
 SERVICE SINK.
 FBC PLUMBING TABLE 403.1 AND 403.2 SEPARATE FACILITIES.
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805?6692
 EMAIL [email protected]
 FAX # 805?6676