2013-04-06 13:21:05 | 6300 SOUTH DIXIE HIGHWAY - SUITES 101 & 102 |
| PERMIT #13020613 |
| REVIEW COMMENTS - FIRE DEPARTMENT |
| |
| REPEAT COMMENT: UPDATE THE CODE LIST TO REFERENCE THE |
| 2010 EDITION OF THE FLORIDA FIRE PREVENTION CODE WHICH |
| CONTAINS THE 2009 EDITION OF BOTH NFPA 1 AND NFPA 101 |
| WITH FLORIDA AMENDMENTS. |
| |
| REPEAT COMMENT: PROVIDE TACTILE SIGNAGE AT ALL REQUIRED |
| EXIT DOORS WITH EXIT SIGNS. |
| |
| REPEAT COMMENT: THE LOCK/LATCH RELEASING MECHANISM ON |
| ALL DOORS SHALL OPEN THE DOOR WITH NOT MORE THAN ONE |
| RELEASING OPERATION. THE RELEASING MECHANISM SHALL HAVE |
| AN OBVIOUS METHOD OF OPERATION THAT IS READILY OPERATED |
| UNDER ALL LIGHTING CONDITIONS. THE RELEASING DEVICE |
| SHOULD BE CAPABLE OF BEING OPERATED WITH ONE HAND AND |
| SHOULD NOT REQUIRE TIGHT GRASPING, TIGHT PINCHING OR |
| TWISTING OF THE WRIST TO OPERATE PER SECTION 7.2.1.5.9 |
| OF NFPA 101 FLORIDA EDITION 2007. |
| |
| REPEAT COMMENT: DOORS SERVING AN OCCUPANT LOAD OF 50 OR |
| MORE PERSONS SHALL SWING IN THE DIRECTION OF EGRESS. |
| |
| REPEAT COMMENT: THE CORRECT OCCUPANCY TYPE NEEDS TO BE |
| DETERMINED BEFORE A THOROUGH AND COMPLETE PLAN REVIEW |
| CAN BE PERFORMED. THE PLANS INDICATE A BUSINESS |
| OCCUPANCY; HOWEVER, AN ASSEMBLY OCCUPANCY IS MORE |
| APPROPRIATE. THE FIRE CODE DEFINES AN ASSEMBLY |
| OCCUPANCY AS AN OCCUPANCY USED FOR THE GATHERING OF 50 |
| OR MORE PERSONS FOR DELIBERATION, WORSHIP, |
| ENTERTAINMENT, EATING, DRINKING OR SIMILAR USAGE. |
| |
| NEW COMMENT: SHEET A-1 INDICATES AN EXERCISE AREA OF |
| 490 SQ.FT.; HOWEVER, THE SCALED MEASUREMENT INDICATES |
| AN AREA OF 800 SQ.FT. (25 FT. X 32 FT.). USING AN |
| OCCUPANT LOAD FACTOR OF 15 SQ.FT. PER PERSON (EXERCISE |
| ROOM WITHOUT EQUIPMENT PER TABLE 7.3.1.2 NFPA 101) |
| RESULTS IN AN OCCUPANT LOAD OF 54 PERSONS. |
| |
| NEW COMMENT: EVERY ASSEMBLY OCCUPANCY ROOM NOT HAVING |
| FIXED SEATS SHALL HAVE THE OCCUPANT LOAD OF THE ROOM |
| POSTED IN A CONSPICUOUS PLACE NEAR THE MAIN EXIT FROM |
| THE ROOM. SIGNS SHALL BE DURABLE AND INDICATE THE |
| NUMBER OF OCCUPANTS PERMITTED FOR EACH ROOM. |
| |
| NEW COMMENT: SHEET A-1, THE "HALL AREA" APPEARS TO BE A |
| LARGE OPEN AREA THAT IS NOT DESIGNATED AS ANY |
| PARTICULAR USE OR OCCUPANT LOAD. MORE INFORMATION (USE, |
| FURNITURE, ETC.) NEEDS TO BE PROVIDED. |
| |
| NEW COMMENT: SHEET A-1, A 1-HOUR FIRE-RATED CEILING |
| BARRIER IS NEEDED FOR THE STORAGE/WATER HEATER AREA |
| LOCATED BENEATH THE CONCRETE STAIRS. |
| |
| WESLEY JOLIN |
| FIRE INVESTIGATOR & INSPECTOR |
| OFFICE OF THE FIRE MARSHAL |
| WEST PALM BEACH FIRE RESCUE |