2013-04-06 13:21:056300 SOUTH DIXIE HIGHWAY - SUITES 101 & 102
 PERMIT #13020613
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 REPEAT COMMENT: UPDATE THE CODE LIST TO REFERENCE THE
 2010 EDITION OF THE FLORIDA FIRE PREVENTION CODE WHICH
 CONTAINS THE 2009 EDITION OF BOTH NFPA 1 AND NFPA 101
 WITH FLORIDA AMENDMENTS.
  
 REPEAT COMMENT: PROVIDE TACTILE SIGNAGE AT ALL REQUIRED
 EXIT DOORS WITH EXIT SIGNS.
  
 REPEAT COMMENT: THE LOCK/LATCH RELEASING MECHANISM ON
 ALL DOORS SHALL OPEN THE DOOR WITH NOT MORE THAN ONE
 RELEASING OPERATION. THE RELEASING MECHANISM SHALL HAVE
 AN OBVIOUS METHOD OF OPERATION THAT IS READILY OPERATED
 UNDER ALL LIGHTING CONDITIONS. THE RELEASING DEVICE
 SHOULD BE CAPABLE OF BEING OPERATED WITH ONE HAND AND
 SHOULD NOT REQUIRE TIGHT GRASPING, TIGHT PINCHING OR
 TWISTING OF THE WRIST TO OPERATE PER SECTION 7.2.1.5.9
 OF NFPA 101 FLORIDA EDITION 2007.
  
 REPEAT COMMENT: DOORS SERVING AN OCCUPANT LOAD OF 50 OR
 MORE PERSONS SHALL SWING IN THE DIRECTION OF EGRESS.
  
 REPEAT COMMENT: THE CORRECT OCCUPANCY TYPE NEEDS TO BE
 DETERMINED BEFORE A THOROUGH AND COMPLETE PLAN REVIEW
 CAN BE PERFORMED. THE PLANS INDICATE A BUSINESS
 OCCUPANCY; HOWEVER, AN ASSEMBLY OCCUPANCY IS MORE
 APPROPRIATE. THE FIRE CODE DEFINES AN ASSEMBLY
 OCCUPANCY AS AN OCCUPANCY USED FOR THE GATHERING OF 50
 OR MORE PERSONS FOR DELIBERATION, WORSHIP,
 ENTERTAINMENT, EATING, DRINKING OR SIMILAR USAGE.
  
 NEW COMMENT: SHEET A-1 INDICATES AN EXERCISE AREA OF
 490 SQ.FT.; HOWEVER, THE SCALED MEASUREMENT INDICATES
 AN AREA OF 800 SQ.FT. (25 FT. X 32 FT.). USING AN
 OCCUPANT LOAD FACTOR OF 15 SQ.FT. PER PERSON (EXERCISE
 ROOM WITHOUT EQUIPMENT PER TABLE 7.3.1.2 NFPA 101)
 RESULTS IN AN OCCUPANT LOAD OF 54 PERSONS.
  
 NEW COMMENT: EVERY ASSEMBLY OCCUPANCY ROOM NOT HAVING
 FIXED SEATS SHALL HAVE THE OCCUPANT LOAD OF THE ROOM
 POSTED IN A CONSPICUOUS PLACE NEAR THE MAIN EXIT FROM
 THE ROOM. SIGNS SHALL BE DURABLE AND INDICATE THE
 NUMBER OF OCCUPANTS PERMITTED FOR EACH ROOM.
  
 NEW COMMENT: SHEET A-1, THE "HALL AREA" APPEARS TO BE A
 LARGE OPEN AREA THAT IS NOT DESIGNATED AS ANY
 PARTICULAR USE OR OCCUPANT LOAD. MORE INFORMATION (USE,
 FURNITURE, ETC.) NEEDS TO BE PROVIDED.
  
 NEW COMMENT: SHEET A-1, A 1-HOUR FIRE-RATED CEILING
 BARRIER IS NEEDED FOR THE STORAGE/WATER HEATER AREA
 LOCATED BENEATH THE CONCRETE STAIRS.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730