2013-04-04 08:35:31 | BUILDING PLAN REVIEW |
| PERMIT: 13020613 |
| ADD: 6300 S DIXIE HWY |
| CONT: ATLANTIDA |
| TEL: (561)313-8126 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 2ND REVIEW |
| DATE: 04/04/2013 |
| ACTION: DENIED |
| |
| 1-2) COMPLIED. |
| |
| |
| 3) 2ND REQUEST, SEMI-COMPLIED. SHEET A-1 NOTE # 4 |
| INDICATES A BUSINESS OCCUPANCY AND THE REFERENECE TO |
| CODE SECTION 306 WHICH IS FACTORY? THEN UNDER THE |
| HEADING NOTES OCCUPANCY TYPE ; ASSEMBLY, THIS IS A YOGA |
| STUDIO, THIS TRUELY APPEARS TO BE A EXERCISE ROOM |
| WITHOUT EQUIPMENT AND THE 15 SQ FT PER PERSON SHOULD BE |
| USED PROVIDE WHAT AREA WILL BE USED FOR YOGA PROVIDE |
| THE SQ FT PER AREA AND OCCUPANT LOADS FOR EACH AREA. |
| THE YOGA AREA AREA IS 490 SQ FT / 15 SQ FT PER OCCUPANT |
| = 33 OCCUPANTS. IF YOU LOOK AT THE SAME AREA 490 SQ FT |
| WITH THE MATS BEING EQUIPMENT, 490/15= 10 OCCUPANTS. |
| PLEASE PROVIDE WHAT METHOD YOU USED TO PROVIDE AN |
| OCCUPANT LOAD OF 15. 2010 FBC-B TABLE 1004.1.1. |
| |
| 4)2ND SHEET 1-A UNDER NOTES CLASSIFIES THIS BUILDING AS |
| A TYPE 5 BUILDING. UNDER THE 2010 FBC-B TABLE 503.1 & |
| TABLE 601 THE TABLES LIST 5A OR 5B. |
| |
| 5-7) COMPLIED. |
| NEW COMMENTS: |
| |
| 8) THE NEW SET OF PLANS HAVE ELIMINATED THE FRONT |
| DOORS, ON THE A-1 SHEET BUT STILL SHOW THEM ON THE LIFE |
| SAFETY PLAN, IS THIS AN OVER SITE, ARE THE DOORS TILL |
| THERE? EXIT DISCHARGE 1027. |
| |
| 9) THE PLANS ALSO SHOW FOR THE FIRST TIME A EXIT FROM |
| THE SECOND STORY BUT THE DETAIL A A-1 INDICATES A ROOF |
| ABOVE, PLEASE CLARIFY WHAT TYPE CONDITION IS LOCATED |
| ABOVE THIS UNIT? IS THERE ANOTHER OCCUPANCY TYPE ABOVE |
| AND HOW ARE YOU OBTAINING OCCUPANCY SEPERATION FROM THE |
| UNIT ABOVE? 2010 FBC-B TABLE 508.4. |
| |
| 10) SHEET A1 WITH THE STAIRWELL FROM THE SECOND FLOOR, |
| IT APPEARS THAT YOU CAN ENTER THE TENANT SPACE THROUGH |
| A BUILDING UTILITY CLOSET, WHERE IS THE TENANT |
| SEPERATION LINE, AND WHY CAN YOU ENTER THE UTILITY |
| CLOSET FROM THE VERTICAL EXIT. THE 2010 FBC-B 1022.4 |
| OPENINGS THROUGH AN EXIT ENCLOSURE ARE PROHIBITED |
| EXCEPT FOR REQUIRED EXIT DOORS.1022.3 OPENINGS IN EXIT |
| ENCLOSURES OTHER THAN UNPROTECTED EXTERIOR OPENINGS |
| SHALL BE LIMITED TO THOSE NECESSARY FOR EXIT ACCESS TO |
| THE ENCLOSURE FROM NORMALLY OCCUPIED SPACES AND FOR |
| EGRESS FROM THE ENCLOSURE. |
| |
| 11) BOTH THE NEW A1 SHEET AS WELL AS THE LS SHEET |
| INDICATE A WATER HEATER IN THE VERTICAL EXIT ENCLOSURE. |
| 2010 FBC-B 1022.4 PENETRATIONS. |
| PENETRATIONS INTO AND OPENINGS THROUGH AN EXIT |
| ENCLOSURE ARE PROHIBITED EXCEPT FOR REQUIRED EXIT |
| DOORS, EQUIPMENT AND DUCTWORK NECESSARY FOR INDEPENDENT |
| VENTILATION OR PRESSURIZATION, SPRINKLER PIPING, |
| STANDPIPES, ELECTRICAL RACEWAY FOR FIRE DEPARTMENT |
| COMMUNICATION SYSTEMS AND ELECTRICAL RACEWAY SERVING |
| THE EXIT ENCLOSURE AND TERMINATING AT A STEEL BOX NOT |
| EXCEEDING 16 SQUARE INCHES (0.010 M2). SUCH |
| PENETRATIONS SHALL BE PROTECTED IN ACCORDANCE WITH |
| SECTION 713. THERE SHALL BE NO PENETRATIONS OR |
| COMMUNICATION OPENINGS, WHETHER PROTECTED OR NOT, |
| BETWEEN ADJACENT EXIT ENCLOSURES. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| CONSTRUCTION SERVICES HOME PAGE |
| HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| |
| PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| |
| MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| |
| |
| |