Plan Review Notes
Plan Review Notes For Permit 13020613
Permit Number 13020613
Review Stop B
Sequence Number 2
Notes
Date Text
2013-04-04 08:35:31BUILDING PLAN REVIEW
 PERMIT: 13020613
 ADD: 6300 S DIXIE HWY
 CONT: ATLANTIDA
 TEL: (561)313-8126
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: 04/04/2013
 ACTION: DENIED
  
 1-2) COMPLIED.
  
  
 3) 2ND REQUEST, SEMI-COMPLIED. SHEET A-1 NOTE # 4
 INDICATES A BUSINESS OCCUPANCY AND THE REFERENECE TO
 CODE SECTION 306 WHICH IS FACTORY? THEN UNDER THE
 HEADING NOTES OCCUPANCY TYPE ; ASSEMBLY, THIS IS A YOGA
 STUDIO, THIS TRUELY APPEARS TO BE A EXERCISE ROOM
 WITHOUT EQUIPMENT AND THE 15 SQ FT PER PERSON SHOULD BE
 USED PROVIDE WHAT AREA WILL BE USED FOR YOGA PROVIDE
 THE SQ FT PER AREA AND OCCUPANT LOADS FOR EACH AREA.
 THE YOGA AREA AREA IS 490 SQ FT / 15 SQ FT PER OCCUPANT
 = 33 OCCUPANTS. IF YOU LOOK AT THE SAME AREA 490 SQ FT
 WITH THE MATS BEING EQUIPMENT, 490/15= 10 OCCUPANTS.
 PLEASE PROVIDE WHAT METHOD YOU USED TO PROVIDE AN
 OCCUPANT LOAD OF 15. 2010 FBC-B TABLE 1004.1.1.
  
 4)2ND SHEET 1-A UNDER NOTES CLASSIFIES THIS BUILDING AS
 A TYPE 5 BUILDING. UNDER THE 2010 FBC-B TABLE 503.1 &
 TABLE 601 THE TABLES LIST 5A OR 5B.
  
 5-7) COMPLIED.
 NEW COMMENTS:
  
 8) THE NEW SET OF PLANS HAVE ELIMINATED THE FRONT
 DOORS, ON THE A-1 SHEET BUT STILL SHOW THEM ON THE LIFE
 SAFETY PLAN, IS THIS AN OVER SITE, ARE THE DOORS TILL
 THERE? EXIT DISCHARGE 1027.
  
 9) THE PLANS ALSO SHOW FOR THE FIRST TIME A EXIT FROM
 THE SECOND STORY BUT THE DETAIL A A-1 INDICATES A ROOF
 ABOVE, PLEASE CLARIFY WHAT TYPE CONDITION IS LOCATED
 ABOVE THIS UNIT? IS THERE ANOTHER OCCUPANCY TYPE ABOVE
 AND HOW ARE YOU OBTAINING OCCUPANCY SEPERATION FROM THE
 UNIT ABOVE? 2010 FBC-B TABLE 508.4.
  
 10) SHEET A1 WITH THE STAIRWELL FROM THE SECOND FLOOR,
 IT APPEARS THAT YOU CAN ENTER THE TENANT SPACE THROUGH
 A BUILDING UTILITY CLOSET, WHERE IS THE TENANT
 SEPERATION LINE, AND WHY CAN YOU ENTER THE UTILITY
 CLOSET FROM THE VERTICAL EXIT. THE 2010 FBC-B 1022.4
 OPENINGS THROUGH AN EXIT ENCLOSURE ARE PROHIBITED
 EXCEPT FOR REQUIRED EXIT DOORS.1022.3 OPENINGS IN EXIT
 ENCLOSURES OTHER THAN UNPROTECTED EXTERIOR OPENINGS
 SHALL BE LIMITED TO THOSE NECESSARY FOR EXIT ACCESS TO
 THE ENCLOSURE FROM NORMALLY OCCUPIED SPACES AND FOR
 EGRESS FROM THE ENCLOSURE.
  
 11) BOTH THE NEW A1 SHEET AS WELL AS THE LS SHEET
 INDICATE A WATER HEATER IN THE VERTICAL EXIT ENCLOSURE.
 2010 FBC-B 1022.4 PENETRATIONS.
 PENETRATIONS INTO AND OPENINGS THROUGH AN EXIT
 ENCLOSURE ARE PROHIBITED EXCEPT FOR REQUIRED EXIT
 DOORS, EQUIPMENT AND DUCTWORK NECESSARY FOR INDEPENDENT
 VENTILATION OR PRESSURIZATION, SPRINKLER PIPING,
 STANDPIPES, ELECTRICAL RACEWAY FOR FIRE DEPARTMENT
 COMMUNICATION SYSTEMS AND ELECTRICAL RACEWAY SERVING
 THE EXIT ENCLOSURE AND TERMINATING AT A STEEL BOX NOT
 EXCEEDING 16 SQUARE INCHES (0.010 M2). SUCH
 PENETRATIONS SHALL BE PROTECTED IN ACCORDANCE WITH
 SECTION 713. THERE SHALL BE NO PENETRATIONS OR
 COMMUNICATION OPENINGS, WHETHER PROTECTED OR NOT,
 BETWEEN ADJACENT EXIT ENCLOSURES.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  