Plan Review Notes For Permit 13020613 |
Permit Number |
13020613 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2013-02-27 15:45:44 | FBC 2010 EXISTING BUILDING CODE | | FBC 2010 ACCESSIBILITY CODE | | FBC 2010 PLUMBING REVIEW #1 | | DENIED: | | | | MORE INFORMATION IS REQUIRED FOR THE OCCUPANCY TYPE AND | | OCCUPANT LOAD. | | SHEET A-1 SCOPE OF WORK NOTE 4 STATES GROUP B BUISNESS | | UNDER NOTES STATES - GROUP M, WITH 35 OCCUPANTS. | | BUSINESS OCCUPANCY WITH 35 OCCUPANTS WOULD REQUIRE 2 | | RESTROOMS AND A HI/LOW DRINKING FOUNTAIN (FBC | | ACCESSIBILITY CODE 211.2) UNLESS THESE ARE PROVIDED IN | | THE BUILDING COMMON AREA. | | FBC PLUMBING TABLE 403.1 WATER CLOSETS 1 PER 25 FOR THE | | FIRST 50 OCCUPANTS. DRINKING FOUNTAIN REQUIRED FOR OVER | | 15 OCCUPANTS. | | | | ALSO A YOGA STUDIO COULD BE AN ASSEMBLY OCCUPANCY. THEN | | SEPARATE FACILITIES ARE REQUIRED FOR EACH SEX, A HI/LOW | | DRINKING FOUNTAIN, AND A SERVICE SINK. | | FBC PLUMBING 403.2 | | | | THIS OCCUPANCY DOES NOT APPEAR TO BE MERCANTILE AS | | GROUP M IS FOR THE DISPLAY AND SALE OF MERCHANDISE AND | | INVOLVES STOCKS OF GOODS, WARES OR MERCHANDISE | | INCIDENTAL TO SUCH PURPOSES... | | FBC 309.1 | | | | REVIEW BY | | LARRY WAGNER | | CHIEF PLUMBING INSPECTOR | | PHONE # 805-6692 | | EMAIL [email protected] | | FAX # 805-6676 | | |
|