Plan Review Notes
Plan Review Notes For Permit 13020613
Permit Number 13020613
Review Stop P
Sequence Number 1
Notes
Date Text
2013-02-27 15:45:44FBC 2010 EXISTING BUILDING CODE
 FBC 2010 ACCESSIBILITY CODE
 FBC 2010 PLUMBING REVIEW #1
 DENIED:
  
 MORE INFORMATION IS REQUIRED FOR THE OCCUPANCY TYPE AND
 OCCUPANT LOAD.
 SHEET A-1 SCOPE OF WORK NOTE 4 STATES GROUP B BUISNESS
 UNDER NOTES STATES - GROUP M, WITH 35 OCCUPANTS.
 BUSINESS OCCUPANCY WITH 35 OCCUPANTS WOULD REQUIRE 2
 RESTROOMS AND A HI/LOW DRINKING FOUNTAIN (FBC
 ACCESSIBILITY CODE 211.2) UNLESS THESE ARE PROVIDED IN
 THE BUILDING COMMON AREA.
 FBC PLUMBING TABLE 403.1 WATER CLOSETS 1 PER 25 FOR THE
 FIRST 50 OCCUPANTS. DRINKING FOUNTAIN REQUIRED FOR OVER
 15 OCCUPANTS.
  
 ALSO A YOGA STUDIO COULD BE AN ASSEMBLY OCCUPANCY. THEN
 SEPARATE FACILITIES ARE REQUIRED FOR EACH SEX, A HI/LOW
 DRINKING FOUNTAIN, AND A SERVICE SINK.
 FBC PLUMBING 403.2
  
 THIS OCCUPANCY DOES NOT APPEAR TO BE MERCANTILE AS
 GROUP M IS FOR THE DISPLAY AND SALE OF MERCHANDISE AND
 INVOLVES STOCKS OF GOODS, WARES OR MERCHANDISE
 INCIDENTAL TO SUCH PURPOSES...
 FBC 309.1
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  