Plan Review Notes
Plan Review Notes For Permit 13020613
Permit Number 13020613
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2013-03-02 19:30:106300 SOUTH DIXIE HIGHWAY - SUITES 101 & 102
 PERMIT #13020613
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 THE PLAN ADDRESS DOES NOT INDICATE IF IT IS NORTH DIXIE
 OR SOUTH DIXIE HIGHWAY.
  
 UPDATE THE CODE LIST TO REFERENCE THE 2010 EDITION OF
 THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE
 2009 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA
 AMENDMENTS.
  
 PROVIDE A LIFE SAFETY PLAN SHOWING ALL EXITS, OCCUPANCY
 TYPES, OCCUPANT LOADS, FIRE RATED WALLS, EXIT SIGNS,
 EMERGENCY LIGHTING, TRAVEL DISTANCES, COMMON PATH OF
 TRAVEL ETC.
  
 SHEET A-1: THE BUILDING SITE LOCATION IS INCORRECTLY
 SHOWN AS "S. MILITARY TRAIL."
  
 PROVIDE AN EXERCISE EQUIPMENT LAYOUT, YOGA MAT LAYOUT,
 ETC.
  
 PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH
 EXIT SIGNS.
  
 THE LOCK/LATCH RELEASING MECHANISM ON ALL DOORS SHALL
 OPEN THE DOOR WITH NOT MORE THAN ONE RELEASING
 OPERATION. THE RELEASING MECHANISM SHALL HAVE AN
 OBVIOUS METHOD OF OPERATION THAT IS READILY OPERATED
 UNDER ALL LIGHTING CONDITIONS. THE RELEASING DEVICE
 SHOULD BE CAPABLE OF BEING OPERATED WITH ONE HAND AND
 SHOULD NOT REQUIRE TIGHT GRASPING, TIGHT PINCHING OR
 TWISTING OF THE WRIST TO OPERATE PER SECTION 7.2.1.5.9
 OF NFPA 101 FLORIDA EDITION 2007.
  
 DOORS SERVING AN OCCUPANT LOAD OF 50 OR MORE PERSONS
 SHALL SWING IN THE DIRECTION OF EGRESS.
  
 THE CORRECT OCCUPANCY TYPE NEEDS TO BE DETERMINED
 BEFORE A THOROUGH AND COMPLETE PLAN REVIEW CAN BE
 PERFORMED. THE PLANS INDICATE BOTH A BUSINESS OCCUPANCY
 AND "M" GROUP (MERCANTILE?); HOWEVER, AN ASSEMBLY
 OCCUPANCY APPEARS TO BE MORE APPROPRIATE.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  