2013-03-02 19:30:10 | 6300 SOUTH DIXIE HIGHWAY - SUITES 101 & 102 |
| PERMIT #13020613 |
| REVIEW COMMENTS - FIRE DEPARTMENT |
| |
| THE PLAN ADDRESS DOES NOT INDICATE IF IT IS NORTH DIXIE |
| OR SOUTH DIXIE HIGHWAY. |
| |
| UPDATE THE CODE LIST TO REFERENCE THE 2010 EDITION OF |
| THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE |
| 2009 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA |
| AMENDMENTS. |
| |
| PROVIDE A LIFE SAFETY PLAN SHOWING ALL EXITS, OCCUPANCY |
| TYPES, OCCUPANT LOADS, FIRE RATED WALLS, EXIT SIGNS, |
| EMERGENCY LIGHTING, TRAVEL DISTANCES, COMMON PATH OF |
| TRAVEL ETC. |
| |
| SHEET A-1: THE BUILDING SITE LOCATION IS INCORRECTLY |
| SHOWN AS "S. MILITARY TRAIL." |
| |
| PROVIDE AN EXERCISE EQUIPMENT LAYOUT, YOGA MAT LAYOUT, |
| ETC. |
| |
| PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH |
| EXIT SIGNS. |
| |
| THE LOCK/LATCH RELEASING MECHANISM ON ALL DOORS SHALL |
| OPEN THE DOOR WITH NOT MORE THAN ONE RELEASING |
| OPERATION. THE RELEASING MECHANISM SHALL HAVE AN |
| OBVIOUS METHOD OF OPERATION THAT IS READILY OPERATED |
| UNDER ALL LIGHTING CONDITIONS. THE RELEASING DEVICE |
| SHOULD BE CAPABLE OF BEING OPERATED WITH ONE HAND AND |
| SHOULD NOT REQUIRE TIGHT GRASPING, TIGHT PINCHING OR |
| TWISTING OF THE WRIST TO OPERATE PER SECTION 7.2.1.5.9 |
| OF NFPA 101 FLORIDA EDITION 2007. |
| |
| DOORS SERVING AN OCCUPANT LOAD OF 50 OR MORE PERSONS |
| SHALL SWING IN THE DIRECTION OF EGRESS. |
| |
| THE CORRECT OCCUPANCY TYPE NEEDS TO BE DETERMINED |
| BEFORE A THOROUGH AND COMPLETE PLAN REVIEW CAN BE |
| PERFORMED. THE PLANS INDICATE BOTH A BUSINESS OCCUPANCY |
| AND "M" GROUP (MERCANTILE?); HOWEVER, AN ASSEMBLY |
| OCCUPANCY APPEARS TO BE MORE APPROPRIATE. |
| |
| WESLEY JOLIN |
| FIRE INVESTIGATOR & INSPECTOR |
| OFFICE OF THE FIRE MARSHAL |
| WEST PALM BEACH FIRE RESCUE |
| [email protected] |
| (561) 805-6730 |
| |