2013-03-01 09:41:48 | BUILDING PLAN REVIEW |
| PERMIT: 13020613 |
| ADD: 6300 S DIXIE HWY |
| CONT: ATLANTIDA |
| TEL: (561)313-8126 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: 03/01/2013 |
| ACTION: DENIED |
| |
| 1) SHEET A1 NOTE # 2, UNDER THE HEADING INDICATES THE |
| USE OF TABLE 302.1.1AND 2 HOUR FIRE WALL RATINGS, IN |
| THE 2010 FBC-B THERE IS NO SUCH TABLE PLEASE UPDATE |
| PLANS TO THE 2010 FBC-B. FIRE WALLS IS THE WRONG |
| TERM,THEY ARE WALLS THAT SPLIT BUILDINGS INTO 2 |
| BUILDINGS BECAUSE OF BEING TO LARGE FOR THE BUILDING |
| TYPE DECLARED SEE 706. THE WALLS ARE TENAN SEPERATION |
| WALLS ( FIRE PARTITIONS 709) OR OCCUPANCY SEPERATION |
| WALLS. |
| |
| 2) SHEET A-1 NOTE # 3 UNDER THE HEADING INDICATES THE |
| USE OF TABLE 302.1.1 AND 1 HOUR FIRE WALLS, IN THE 2010 |
| FBC-B THERE IS NO SUCH TABLE PLEASE UPDATE PLANS TO THE |
| 2010 FBC-B. |
| |
| 3) SHEET A-1 NOTE # 4 INDICATES A BUSINESS OCCUPANCY |
| AND THE REFERENECE TO CODE SECTION 306 WHICH IS |
| FACTORY? THEN UNDER THE HEADING NOTES OCCUPANCY TYPE ; |
| MERCANTILE, THIS IS A YOGA SSTUDIO, PROVIDE THE AREA ON |
| THE PLAN WHERE THE MERCANTILE AREA IS LOCATED. THIS |
| TRUELY APPEARS TO BE A EXERCISE ROOM WITHOUT EQUIPMENT |
| AND THE 15 SQ FT PER PERSON SHOULD BE USED PROVIDE WHAT |
| AREA WILL BE USED FOR YOGA AND WHAT AREA WILL BE USED |
| AS MERCANTILE FOR THE SALE OF GOODS, PROVIDE THE SQ FT |
| PER AREA AND OCCUPANT LOADS FOR EACH AREA. DEPENDING ON |
| THE SQ FOOTAGE THIS MAY BE A MIXED USE WILL THERE BE |
| SEPERATION BETWEEN OCCUPANCIES OR NON SEPERATED USE OR |
| ACCESSORY OCCUPANCIE? 508.4, 508.3 OR 508.2. |
| |
| 4) SHEET 1-A UNDER NOTES CLASSIFIES THIS BUILDING AS A |
| TYPE III BUILDING UNDER THE 2001 AND EARLIER CODE A |
| TYPE III BUILDING IDENTIFICATION WAS USED FOR A HEAVY |
| TIMBER BUILDING, PLEASE USE THE NOMENCLATURE UNDER THE |
| 2010 FBC-B TABLE 503.1 & TABLE 601. |
| |
| 5) THE WIND DESIGN CRITERIA IS NOT STATED TO THE 2010 |
| FBC-B AND WIND CRITERIA FOR A CATEGORY II BUILDING V |
| ULT 170 MPH, 3 SECOND GUST |
| |
| 6) UNDER THE WIND DESIGN CRITERIA THE EXPOSURE IS |
| LISTED AS "M" ? 2010 FBC-B 1609. 4.2 SURFACE ROUGHNESS |
| "C". |
| |
| 7) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| INFORMATION. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| CONSTRUCTION SERVICES HOME PAGE |
| HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| |
| PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| |
| MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| |
| |
| |