2013-04-22 08:32:33 | BUILDING PLAN REVIEW |
| PERMIT: 13020602 |
| ADD: 2555 PALM BCH LAKES # 100 |
| CONT: FISHER CONTRACTING |
| TEL: (561)691-4716 |
| 2010 FLORIDA BUILDING CODE W |
| * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 2ND REVIEW |
| DATE: 4/22/2013 |
| ACTION: DENIED |
| |
| 1) COMPLIED. |
| |
| 2) 2ND REQUEST, PLEASE PROVIDE ADDITIONAL DATA FOR THE |
| WATER CURTAIN IN THE MAIN LOBBY, WATER CURTAINS ARE TO |
| BE INSTALLED IN AN ATRIUM MEETING ALL THE REQUIEMENTS |
| OF AN ATRIUM WITH SMOKE CONTROL PER 2010 FBC-B909. |
| EXIST BLDG CODE 704.2.1 FIRE PROTECTION SEE SECTION 403 |
| OF THE FBC-B. 403.6 SMOKE REMOVAL SHALL BE PROVIDED IN |
| ACCORDANCE WITH 909 FBC-B. SHEET A-1 INDICATES THAT THE |
| COMMON WALL TO THE ATRIUM IS A GLASS CURTAIN WALL TYPE |
| OF CONSTRUCTION WITH SPRINKLER HEADS ABOVE IN THE MAIN |
| LOBBY, WE TAKE THE MEANING OF SPRINKLER HEADS IN THE |
| MAIN LOBBY TO MEAN AT THE TOP OF THE ATRIUM. |
| |
| THE EXCEPTION TO THE ONE HOUR RATED FIRE BARRIER IS |
| 404.6 EXCEPTION # 1. A GLASS WALL FORMING A SMOKE |
| PARTITION WHERE AUTOMATIC SPRINKLERS ARE SPACED 6 FEET |
| (1829 MM) OR LESS ALONG BOTH SIDES OF THE SEPARATION |
| WALL, OR ON THE ROOM SIDE ONLY IF THERE IS NOT A |
| WALKWAY ON THE ATRIUM SIDE, AND BETWEEN 4 INCHES AND 12 |
| INCHES (102 MM AND 305 MM) AWAY FROM THE GLASS AND |
| DESIGNED SO THAT THE ENTIRE SURFACE OF THE GLASS IS WET |
| UPON ACTIVATION OF THE SPRINKLER SYSTEM WITHOUT |
| OBSTRUCTION. THE GLASS SHALL BE INSTALLED IN A GASKETED |
| FRAME SO THAT THE FRAMING SYSTEM DEFLECTS WITHOUT |
| BREAKING (LOADING) THE GLASS BEFORE THE SPRINKLER |
| SYSTEM OPERATES. |
| |
| IS RAISES THE QUESTION WITH CURTAIN WALL CONSTRUCTION, |
| IS THERE INTERMEDIATE HORIZONTAL MULLIONS THAT WOULD |
| KEEP THE WATER FROM THE FIRE SPRINLERS FROM STAYING ON |
| THE GLASS, OR IF THERE IS ORIZONTAL MULLIONS THEN THE |
| FIRE CURTAIN IS IN-EFFECTIVE. |
| |
| 3) COMPLIED. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| CONSTRUCTION SERVICES HOME PAGE |
| HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| |
| PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| |
| MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| |