Plan Review Notes
Plan Review Notes For Permit 13020602
Permit Number 13020602
Review Stop M
Sequence Number 1
Notes
Date Text
2013-03-21 09:21:53PLANS DENIED
 1) PROVIDE DUCT SMOKE DETECTORS ON AHU 1 & 3
 PER SECTION 606.2.1 SUPPLY AIR SYSTEM 2010 FBC (M)
 2) REFER TO SECTION 606.4.1 SUPERVISION 2010 FBC (M)
 3) PROVIDE FRESH AIR DUCT ON AHU # 3
 4) REFER TO SECTION 403.3 OUTDOOR AIR FLOW RATE AND
 TABLE 403.3 MINIMUM VENTILATION RATES 2010 FBC (M)
 5) PROVIDE DUCT SIZE ON ALL DUCT. PER SECTION 107 FBC
 PLAN REVIEW BY HAROLD MOSER