Plan Review Notes For Permit 13020602 |
Permit Number |
13020602 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2013-03-21 09:21:53 | PLANS DENIED | | 1) PROVIDE DUCT SMOKE DETECTORS ON AHU 1 & 3 | | PER SECTION 606.2.1 SUPPLY AIR SYSTEM 2010 FBC (M) | | 2) REFER TO SECTION 606.4.1 SUPERVISION 2010 FBC (M) | | 3) PROVIDE FRESH AIR DUCT ON AHU # 3 | | 4) REFER TO SECTION 403.3 OUTDOOR AIR FLOW RATE AND | | TABLE 403.3 MINIMUM VENTILATION RATES 2010 FBC (M) | | 5) PROVIDE DUCT SIZE ON ALL DUCT. PER SECTION 107 FBC | | PLAN REVIEW BY HAROLD MOSER | | 561-805-6732 | | [email protected] |
|