Plan Review Notes
Plan Review Notes For Permit 13020602
Permit Number 13020602
Review Stop E
Sequence Number 1
Notes
Date Text
2013-03-14 11:02:41 
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS.
  
 GFCI PROTECTION IS REQUIRED FOR ELECTRIC WATER COOLERS.
 NEC 422.52
  
 WIRING IN ALL PATIENT CARE AREAS / EXAM ROOMS REQUIRES
 A SPECIFIC LISTED WIRING METHOD THAT PROVIDES REDUNDANT
 GROUNDING AND INCLUDES AN INSULATED COPPER EQUIPMENT
 GROUND. NEC 517.13
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER