2013-03-12 13:59:51 | BUILDING PLAN REVIEW |
| PERMIT: 13020602 |
| ADD: 2555 PALM BCH LAKES # 100 |
| CONT: FISHER CONTRACTING |
| TEL: (561)691-4716 |
| 2010 FLORIDA BUILDING CODE W |
| * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: 3/12/2013 |
| ACTION: DENIED |
| |
| 1) BUILDING DATA INDICATES THIS TO BE A TYPE III |
| BUILDING, PLEASE REVIEW THE 2010 FBC-B TABLE 503 FOR A |
| 15 STORY BUILDING IT HAS TO BE BUILDING TYPE IA. |
| |
| 2) PLEASE PROVIDE ADDITIONAL DATA FOR THE WATER CURTAIN |
| IN THE MAIN LOBBY, WATER CURTAINS ARE TO BE INSTALLED |
| IN AN ATRIUM MEETING ALL THE REQUIEMENTS OF AN ATRIUM |
| WITH SMOKE CONTROL PER 2010 FBC-B909. EXIST BLDG CODE |
| 704.2.1 FIRE PROTECTION SEE SECTION 403 OF THE FBC-B. |
| 403.6 SMOKE REMOVAL SHALL BE PROVIDED IN ACCORDANCE |
| WITH 909 FBC-B. |
| |
| 3) SHEET A-3 INDICATES A FIRE SPRAY PLAN, A NOTE THAT |
| INDICATES FIRE SPRAY THE ENTIRE ROOF STRUCTURES AS |
| SHOWN , AND THE PLAN IS THE INTERIOR SPACE OF UNIT # |
| 100. ADDITIONAL INFORMATION REQUIRED, 107.2.1.3. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| CONSTRUCTION SERVICES HOME PAGE |
| HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| |
| PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| |
| MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| |
| |
| |
| |