Plan Review Notes For Permit 13020348 |
Permit Number |
13020348 |
|
Review Stop |
G |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2013-02-20 15:48:37 | FBC 2010 FUEL GAS REVIEW #1 | | DENIED: | | | | PLEASE SUBMIT THE FOLLOWING FOR A FUEL GAS REVIEW:: | | | | 2. SHOW TYPE OF PIPING MATERIAL BEING INSTALLED, ALL | | PIPE SIZES, AND THE EDH NUMBER OF CORRUGATED STAINLESS | | STEEL TUBING FOR EACH PIPE SIZE IF BEING USED. | | 3. TYPE OF GAS, (LP OR NATURAL). | | 4. BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU LOAD ON | | THE SYSTEM. REFER TO THE FBC-2010 FUEL GAS SECS. 401.8 | | THRU 402.6.1 AND TABLES 402.4(1) THRU 402.4(35) | | | | | | REVIEW BY | | LARRY WAGNER | | CHIEF PLUMBING INSPECTOR | | PHONE # 805-6692 | | EMAIL [email protected] | | FAX # 805-6676 | | | | |
|