Plan Review Notes
Plan Review Notes For Permit 13020348
Permit Number 13020348
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2013-02-25 14:50:561616 NORTH FLORIDA MANGO ROAD
 PERMIT #13020348
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 DESIGN SHALL CONFORM TO THE 2010 EDITION OF THE FLORIDA
 FIRE PREVENTION CODE WHICH CONTAINS THE 2009 EDITION OF
 BOTH NFPA 1 AND NFPA 101 WITH FLORIDA AMENDMENTS.
  
 OPERATIONS INVOLVING THE SPRAY APPLICATION OF FLAMMABLE
 AND COMBUSTIBLE MATERIALS SHALL COMPLY WITH NFPA 33
 (2007 EDITION).
  
 MIXING ROOMS AND SPRAY AREAS (WHICH INCLUDE EXHAUST
 PLENUMS, EXHAUST DUCTWORK, FILTERS, ETC.) SHALL BE
 PROTECTED WITH AN APPROVED AUTOMATIC FIRE PROTECTION
 SYSTEM.
  
 MIXING ROOMS AND SPRAY BOOTHS SHALL BE CONSTRUCTED OF
 AND SEPARATED FROM SURROUNDING AREAS OF THE BUILDING BY
 CONSTRUCTION ASSEMBLIES THAT HAVE A FIRE RESISTANCE
 RATING OF 1-HOUR.
  
 MIXING ROOM SHALL BE DESIGNED TO CONTAIN A SPILL OF THE
 CONTENTS IN THE ROOM.
  
 AREAS ADJACENT TO THE MIXING ROOM AND SPRAY BOOTH SHALL
 HAVE PERMANENT SIGNS INDICATING, "NO SMOKING OR OPEN
 FLAMES PERMITTED."
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  
  
  
  