Plan Review Notes For Permit 13020348 |
Permit Number |
13020348 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2013-02-26 09:25:52 | 13020348 | | 1616 N. FLORIDA MANGO ROAD #C8 | | PAINT SPRAY BOOTH | | | | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING | | REVIEW COMMENTS. | | | | THE SPRAY BOOTH, MIXING ROOMS AND ALL AREAS WITHIN 3 | | FEET MUST BE CLASSIFIED FOR THE HAZARD. INDICATE ON THE | | PLANS THE APPROPRIATE CLASSIFICATION AND ELECTRICAL | | WIRING METHOD. | | NEC 516.3(C)(2) | | | | PROVIDE A LISTING FROM A NATIONALLY REGISTERED TESTING | | LABORATORY FOR THE SPRAY BOOTH AND PAINT MIXING ROOM. | | NEC 110.3 | | | | ROBERT LECKY | | ELECTRICAL PLANS EXAMINER | | [email protected] | | 561-805-6718 | | | | |
|