Plan Review Notes
Plan Review Notes For Permit 13020348
Permit Number 13020348
Review Stop E
Sequence Number 1
Notes
Date Text
2013-02-26 09:25:5213020348
 1616 N. FLORIDA MANGO ROAD #C8
 PAINT SPRAY BOOTH
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS.
  
 THE SPRAY BOOTH, MIXING ROOMS AND ALL AREAS WITHIN 3
 FEET MUST BE CLASSIFIED FOR THE HAZARD. INDICATE ON THE
 PLANS THE APPROPRIATE CLASSIFICATION AND ELECTRICAL
 WIRING METHOD.
 NEC 516.3(C)(2)
  
 PROVIDE A LISTING FROM A NATIONALLY REGISTERED TESTING
 LABORATORY FOR THE SPRAY BOOTH AND PAINT MIXING ROOM.
 NEC 110.3
  