Plan Review Notes
Plan Review Notes For Permit 13020348
Permit Number 13020348
Review Stop B
Sequence Number 1
Notes
Date Text
2013-02-22 08:50:49BUILDING PLAN REVIEW
 PERMIT: 13020348
 ADD: 1616 N FLORIDA MANGO
 CONT: BADER'S GROUP
 TEL: (561)294-4070
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 REVIEW
 DATE: 02/22/2013
 ACTION: DENIED
  
 1) PLEASE SHOW CODE COMPLIANCE WITH 2010 FBC-B:
  
 1A) [F] 416.2 SPRAY ROOMS. SPRAY ROOMS SHALL BE
 ENCLOSED WITH NOT LESS THAN 1-HOUR FIRE BARRIERS
 CONSTRUCTED IN ACCORDANCE WITH SECTION 707 OR
 HORIZONTAL ASSEMBLIES CONSTRUCTED IN ACCORDANCE WITH
 SECTION 712, OR BOTH. FLOORS SHALL BE WATERPROOFED AND
 DRAINED IN AN APPROVED MANNER.
  
 1B) [F] 416.2.1 SURFACES. THE INTERIOR SURFACES OF
 SPRAY ROOMS SHALL BE SMOOTH AND SHALL BE SO CONSTRUCTED
 TO PERMIT THE FREE PASSAGE OF EXHAUST AIR FROM ALL
 PARTS OF THE INTERIOR AND TO FACILITATE WASHING AND
 CLEANING, AND SHALL BE SO DESIGNED TO CONFINE RESIDUES
 WITHIN THE ROOM. ALUMINUM SHALL NOT BE USED.
  
 1C) [F] 416.3 SPRAYING SPACES. SPRAYING SPACES SHALL BE
 VENTILATED WITH AN EXHAUST SYSTEM TO PREVENT THE
 ACCUMULATION OF FLAMMABLE MIST OR VAPORS IN ACCORDANCE
 WITH THE FLORIDA BUILDING CODE, MECHANICAL. WHERE SUCH
 SPACES ARE NOT SEPARATELY ENCLOSED, NONCOMBUSTIBLE
 SPRAY CURTAINS SHALL BE PROVIDED TO RESTRICT THE SPREAD
 OF FLAMMABLE VAPORS.
  
 1D) [F] 416.3.1 SURFACES. THE INTERIOR SURFACES OF
 SPRAYING SPACES SHALL BE SMOOTH AND CONTINUOUS WITHOUT
 EDGES; SHALL BE SO CONSTRUCTED TO PERMIT THE FREE
 PASSAGE OF EXHAUST AIR FROM ALL PARTS OF THE INTERIOR
 AND TO FACILITATE WASHING AND CLEANING; AND SHALL BE SO
 DESIGNED TO CONFINE RESIDUES WITHIN THE SPRAYING SPACE.
 ALUMINUM SHALL NOT BE USED.
  
 1E) [F] 416.4 SPRAY BOOTHS. SPRAY BOOTHS SHALL BE
 DESIGNED, CONSTRUCTED AND OPERATED IN ACCORDANCE WITH
 THE FLORIDA FIRE PREVENTION CODE.
  
 1F) [F] 416.5 FIRE PROTECTION. AN AUTOMATIC
 FIRE-EXTINGUISHING SYSTEM SHALL BE PROVIDED IN ALL
 SPRAY, DIP AND IMMERSING SPACES AND STORAGE ROOMS AND
 SHALL BE INSTALLED IN ACCORDANCE WITH CHAPTER 9.
  
 2A) PLEASE PROVIDE AMOUNTS OF FLAMABLE OR COMBUSTILE
 LIQUIDS THAT ARE GOING TO BE USED, DISPENSED OR MIXED
 IN OPEN CONTAINERS WITHIN THE MIXING ROOM, THIS WILL
 CLASSIFY TYPE OF OCCUPANCY. SECTION 415, AND TABLE
 307.1(1) MAXIMUM ALLOWABLE QUANITIES PER CONTROL AREA
 OF HAZARDOUS MATERIALS, CLASS I, II AND III FLAMMABLE
 OR COMBUSTIBLE LIQUIDS.
  
 2B) 414.2.1 FIRE-RESISTANCE-RATING REQUIREMENTS.
 CONSTRUCTION REQUIREMENTS. CONTROL AREAS SHALL BE
 SEPARATED FROM EACH OTHER BY FIRE BARRIERS CONSTRUCTED
 IN ACCORDANCE WITH SECTION 707 OR HORIZONTAL ASSEMBLIES
 CONSTRUCTED IN ACCORDANCE WITH SECTION 712, OR BOTH.
  
 2C) [F] 414.2.3 NUMBER. THE MAXIMUM NUMBER OF CONTROL
 AREAS WITHIN A BUILDING SHALL BE IN ACCORDANCE WITH
 TABLE 414.2.2.
  
 3) SHEET A1 INDICATES VENTING THROUGH THE ROOF,
 APPROXIMATELY 4'-0" & 7'-0" , HOW ARE THESE ROOF VENTS
 BE HELD IN PLACE IN THE EVENT OF A HIGH WIND EVENT?
 1609. COMPONENTS & CLADDING.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  