Plan Review Notes For Permit 13020261 |
Permit Number |
13020261 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2013-03-05 09:07:31 | FIRE PLAN REVIEW | | PERMIT # 13020261 | | ADDRESS: 4801 DREHER TRAIL | | CONTRACTOR: DIG IT UNLIMITED 561-748-9758 | | ACTION: DENIED | | | | FLORIDA FIRE PREVENTION CODE 2010 EDITION | | | | 1. INDICATE ON THE PLANS THE TANK SIZE. | | | | 2. INDICATE IF THIS IS A VERTICLE OR HORIZONTAL TANK. | | | | 3. ARE THERE BALLARDS, FENCING OR OTHER BARRIERS TO | | PROTECT THE TANK. | | | | 4. WHAT ARE THE FIRE RATING OF THE ANCHORS. | | | | 5. WHAT MATERIAL TO BE USED TO PROTECT THE TANK | | SUPPORTS NEEDS TO BE 2 HOUR FIRE RESISTANCE RATING. | | | | 6. REFERENCE CODE TO SEE HOW FAR AWAY FROM THE BUIDING | | THE TANK MUST BE AND INDICATE ON PLANS. | | | | 7. INDICATE LABELS NO SMOKING / HAZARD PLACARDS | | | | DERRICK L. DANIELS, BATTALION CHIEF / FIRE MARSHAL | | WEST PALM BEACH FIRE RESCUE | | OFFICE OF THE FIRE MARSHAL | | (561) 804-4709 | | [email protected] | | |
|