Plan Review Notes For Permit 13020240 |
Permit Number |
13020240 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2013-03-04 12:16:29 | PROVISO: | | | | SAFE WORKING CLEARANCES AND DEDICATED WORKING SPACE IS | | REQUIRED AT ALL ELECTRICAL PANEL BOARDS. NEC 110.26, | | 240.24 | | | | THE BOWLING MACHINES AND THE AV EQUIPMENT MUST BE | | LISTED BY A NATIONALLY RECOGNIZED TESTING LABORATORY | | (NRTL). NEC 110.3, 600.3 | | | | SAFETY LABELING IS REQUIRED FOR ELECTRICAL DISCONNECTS | | AND FOR FLASH PROTECTION. NEC 110.22, 110.16 | | | | SEPARATE PERMITS ARE REQUIRED FOR VOICE AND DATA AND | | FIRE ALARM SYSTEMS. | | |
|