2013-02-21 12:09:59 | 13020220 |
| 2003 N. TAMARIND AVE |
| RESIDENTIAL REPAIR |
| |
| PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING |
| ELECTRICAL REVIEW COMMENTS. |
| |
| ELECTRICAL PLANS ARE REQUIRED. PROVIDE AN ELECTRICAL |
| RISER PLAN SHOWING THE PANEL, MAIN BREAKER, GROUNDING, |
| FEEDERS AND BRANCH CIRCUITS. INCLUDE A LOAD CALCULATION |
| AND PANEL DIRECTORY. SHOW LOCATION OF THE ELECTRICAL |
| PANEL WITH REQUIRED SAFE WORKING CLEARANCES. |
| INDICATE THE SIZE AND LOCATION OF THE ELECTRICAL PANEL. |
| ON A FLOOR PLAN SHOW THE LOCATION OF ALL NEW LIGHTING |
| OUTLETS, RECEPTACLE OUTLETS AND SMOKE DETECTORS. NEC |
| 215.5, 210.50, 110.26 |
| |
| SHOW SAFETY CLEARANCES AND LOCATIONS OF ALL APPLIANCES, |
| PANEL BOARDS, METERS ETC. FBC 107.2.1 |
| |
| SHOW THE KITCHEN COUNTER TOP RECEPTACLES TO BE GFCI |
| PROTECTED. NEC 210.8 |
| |
| REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO |
| INCLUDE INTERCONNECTED SMOKE ALARMS BOTH WITHIN AND |
| OUTSIDE EACH SLEEPING AREA. IF THE RESIDENCE HAS GAS |
| APPLIANCES, AN ATTACHED GARAGE OR A FIRE PLACE A CARBON |
| MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET OF EACH |
| ROOM USED FOR SLEEPING. 2010 FBC R314, 315 |
| |
| NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11 |
| |
| ARC FAULT CIRCUIT PROTECTION IS REQUIRED FOR ALL NEW |
| GENERAL PURPOSE OUTLETS INCLUDING LIGHTING. NEC 210.12 |
| |
| THE BATHROOM REQUIRES A DEDICATED 20 AMP BRANCH |
| CIRCUIT. NEC 210.11 (C) (3) |
| |
| A GFCI PROTECTED RECEPTACLE IS REQUIRED OUTSIDE AT THE |
| FRONT AND BACK ENTRANCE AREA. NEC 210.52 (E) (1) |
| |
| |
| ROBERT LECKY |
| ELECTRICAL PLANS EXAMINER |