 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 ELECTRICAL REVIEW COMMENTS.
  
 ELECTRICAL PLANS ARE REQUIRED. PROVIDE AN ELECTRICAL
 RISER PLAN SHOWING THE PANEL, MAIN BREAKER, GROUNDING,
 FEEDERS AND BRANCH CIRCUITS. INCLUDE A LOAD CALCULATION
 AND PANEL DIRECTORY. SHOW LOCATION OF THE ELECTRICAL
 PANEL WITH REQUIRED SAFE WORKING CLEARANCES.
 INDICATE THE SIZE AND LOCATION OF THE ELECTRICAL PANEL.
 ON A FLOOR PLAN SHOW THE LOCATION OF ALL NEW LIGHTING
 OUTLETS, RECEPTACLE OUTLETS AND SMOKE DETECTORS. NEC
 215.5, 210.50, 110.26
  
 SHOW SAFETY CLEARANCES AND LOCATIONS OF ALL APPLIANCES,
 PANEL BOARDS, METERS ETC. FBC 107.2.1
  
 SHOW THE KITCHEN COUNTER TOP RECEPTACLES TO BE GFCI
 PROTECTED. NEC 210.8
  
 REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO
 INCLUDE INTERCONNECTED SMOKE ALARMS BOTH WITHIN AND
 OUTSIDE EACH SLEEPING AREA. IF THE RESIDENCE HAS GAS
 APPLIANCES, AN ATTACHED GARAGE OR A FIRE PLACE A CARBON
 MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET OF EACH
 ROOM USED FOR SLEEPING. 2010 FBC R314, 315
  
 NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11
  
 ARC FAULT CIRCUIT PROTECTION IS REQUIRED FOR ALL NEW
 GENERAL PURPOSE OUTLETS INCLUDING LIGHTING. NEC 210.12
  
 THE BATHROOM REQUIRES A DEDICATED 20 AMP BRANCH
 CIRCUIT. NEC 210.11 (C) (3)
  
 A GFCI PROTECTED RECEPTACLE IS REQUIRED OUTSIDE AT THE
 FRONT AND BACK ENTRANCE AREA. NEC 210.52 (E) (1)
  
  