Plan Review Notes For Permit 13020219 |
Permit Number |
13020219 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2013-04-01 12:40:27 | | | 13020219 | | 817 21ST STREET | | RESIDENTIAL REPAIR | | | | THE PERMIT WAS APPROVED WITH THE FOLLOWING REQUIREMENTS | | LISTED ON THE PLAN. | | | | PROVISO | | | | KITCHEN COUNTER TOP RECEPTACLES TO BE GFCI PROTECTED. | | NEC 210.8 | | | | REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO | | INCLUDE INTERCONNECTED SMOKE ALARMS BOTH WITHIN AND | | OUTSIDE EACH SLEEPING AREA. IF THE RESIDENCE HAS GAS | | APPLIANCES, AN ATTACHED GARAGE OR A FIRE PLACE A CARBON | | MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET OF EACH | | ROOM USED FOR SLEEPING. 2010 FBC R314, 315 | | | | NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11 | | | | ARC FAULT CIRCUIT PROTECTION IS REQUIRED FOR ALL NEW | | GENERAL PURPOSE OUTLETS INCLUDING LIGHTING. NEC 210.12 | | | | THE BATHROOM REQUIRES A DEDICATED 20 AMP BRANCH | | CIRCUIT. NEC 210.11 (C) (3) | | | | A GFCI PROTECTED RECEPTACLE IS REQUIRED OUTSIDE AT THE | | FRONT AND BACK ENTRANCE AREA. NEC 210.52 (E) (1) | | | | AN INTERSYSTEM BONDING STRIP IS REQUIRED AT THE MAIN | | SERVICE GROUND. NEC 250.94 | | | | | | ROBERT LECKY | | ELECTRICAL PLANS EXAMINER | | [email protected] | | 561-805-6718 | | |
|