2013-04-22 14:10:50 | 701 SOUTH ROSEMARY AVENUE - SUITE #316 |
| PERMIT #13020210 |
| REVIEW COMMENTS - FIRE DEPARTMENT |
| |
| RESPONSE COMMENT: RELIANCE ON THE TENANT TO MAINTAIN |
| CLEAR AISLES HAS NOT BEEN SUCCESSFUL. PLEASE PROVIDE |
| FLOOR MARKINGS, BOLLARDS, OR DIFFERENT FLOORING |
| MATERIAL SO EGRESS AISLES WILL ALWAYS BE READILY |
| IDENTIFIABLE NO MATTER HOW THE MERCHANDISE AND DISPLAYS |
| CHANGE. |
| ORIGINAL COMMENT: SHEET A-100: PLANS STATE THAT A CLEAR |
| WIDTH OF 3'-0" AND 3'-8" IS TO BE MAINTAINED FOR |
| EXITING; PLEASE INDICATE HOW THIS WILL BE ACCOMPLISHED |
| AND MAINTAINED. |
| |
| RESPONSE COMMENT: THE FIRE PROTECTION INFORMATION FROM |
| THE ORIGINAL COMMENT NEEDS TO BE SUBMITTED EVEN IF THE |
| DESIGN IS A PERFORMANCE SPECIFICATION. FOR ISSUANCE OF |
| A GENERAL BUILDING PERMIT, SECTION 105.3.1.2(2) OF THE |
| FLORIDA BUILDING CODE REQUIRES SEALED FIRE PROTECTION |
| CONSTRUCTION DOCUMENTS FOR THE DESIGN OR ALTERATION OF |
| 50 OR MORE AUTOMATIC FIRE SPRINKLERS. AFTER THE |
| BUILDING PERMIT HAS BEEN ISSUED, THE SPRINKLER |
| CONTRACTOR CAN THEN SUBMIT SHOP DRAWINGS (CONFORMING TO |
| THE ENGINEERED CONSTRUCTION DOCUMENTS) FOR A |
| SUB-PERMIT. |
| ORIGINAL COMMENT: SHEET FP-210: PER FLORIDA |
| ADMINISTRATIVE CODE SECTION 61G15-32.004, FIRE |
| PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE |
| POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF |
| APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT, |
| CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR |
| AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER |
| SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA) |
| AND ANY PERFORMANCE BASED INFORMATION SUCH AS |
| PRE-ENGINEERED SYSTEMS. |
| |
| WESLEY JOLIN |
| FIRE INVESTIGATOR & INSPECTOR |
| OFFICE OF THE FIRE MARSHAL |
| WEST PALM BEACH FIRE RESCUE |
| [email protected] |
| (561) 805-6730 |