2013-04-26 12:15:15 | BUILDING PLAN REVIEW |
| PERMIT:13020210 |
| ADD: 701 S ROSEMARY AVE. SUITE # NOT PROVIDED |
| CONT: LAKEVIEW CONSTRUCTION |
| TEL: (561)635-6935 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| CITY PLACE MANAGEMENT |
| CARLOS BERNEL |
| 561-820-0074 |
| |
| 2ND REVIEW |
| DATE: 04/26/2013 |
| ACTION: DENIED |
| INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. |
| A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. NO |
| TRANSMITTAL LETTER WAS SUBMITTED |
| FOR BUILDINGS FIRST ROUND OF COMMENTS. |
| |
| ADDRESS: THIS PERMIT HAS NOT BEEN PROVIDED WITH THE |
| TENANT SUITE NUMBER. ON THE PERMIT APPLICATION AS WELL |
| AS PLANS H & M'S OWN STORE NUMBER US 316 HAS BEEN |
| MISTAKEN AS THE SUITE NUMBER. PLEASE CORRECT THE PERMIT |
| APPLICATION AND PLANS AND PROVIDE THE TENANT SUITE |
| NUMBER. |
| |
| 1) 2ND REQUEST. THE COVER SHEET INDICATES ALL |
| STOREFRONT TO BE FILED UNDER SEPERATE PERMIT. PLEASE |
| REMOVE THE MENTION OF STOREFRONT FROM THESE PLANS SINCE |
| IT IS NOT PART OF THIS PERMIT. TODATE NO SUCH PERMIT |
| HAS BEEN APPLIED FOR. |
| 2010 WPB ADMINISTRATIVE CODE 107.2.1 INFORMATION ON |
| CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE |
| OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE |
| AND EXTENT OF THE WORK PROPOSED... EXAMPLES ARE A200.00 |
| NOTE # 1 & A-600.00 ELEVATIONS. |
| |
| 2) 2ND REQUEST. SHEET A-200.00 THE TENANT SEPERATION |
| WALLS: |
| 2A) SHEETS 700.00 - 703.00 PROVIDE THE WALL TYPES THAT |
| WERE IDENTIFIIED ON A-200.00. A COMMON NOTE ON WALL |
| SECTION TYPES ALIGN STUD KNOCK OUTS. ARE THESE DETAILS |
| INDICATING NEW WALLS NEXT TO THE EXISTING TENANT |
| SEPERATION WALLS WHERE THE STUD KNOK OUTS CAN BE |
| ALIGNED OR IS THE 5/8 INCH FIRE RATED DRYWALL BEING |
| REMOVED TO PUNCH NEW HOLES IN WHERE THEY DO NOT ALIGN? |
| 107.2.1.3 ADDITIONAL INFORMATION REQUIRED. |
| |
| 2B) THE WALL TAGS FOR THE TENAT SEPERATION WALLS ARE TO |
| BE 1 HOUR PER 2010 FBC-B 709.6.1. ON THE SHEETS 700.00- |
| 702.00 THEY DO NOT INDICATE THEY ARE ONE HOUR FIRE |
| RATED. WALL TYPES L & P ARE INDICATED AS ONE HOUR |
| WALLS, WHY ARE THE OTHER WALL TAGS FOUND ON THE TENANT |
| SEPERATION DESIGNATED AS ONE HOUR? |
| |
| 2C) VARIOUS WALLS INDICATE BEING FURRED OUT WITH FIRE |
| RETARDANT TREATED 3/4 INCH PLYWOOD, PLEASE PROVIDE |
| COMPLIANCE WITH 2010 FBC-B 803.11.1 PLEASE PROVIDE |
| WHICH OF THE THREE OPTIONS WILL BE INSTALLED AT THE |
| SITE. |
| |
| 3) 2ND REQUEST. SHEET S010.00 DO PROVIDE THE WIND |
| DESIGN CRITERIA IF THE WINDOWS ARE TO BE PART OF THIS |
| PERMIT. IF THE WINDOWS ARE TO BE INSTALLED AS PART OF |
| THIS PERMIT THEN THE PRESSURES WILL NEED TO BE PROVIDED |
| FOR THESE OPENINGS AND TTHE HEIGHT FACTOR FOR A THREE |
| STORY BUILDING. |
| THE PLANS INDICATE THE BUILDING TO BE 15 FEET TALL WITH |
| ASSOCIATED PRESSURES. 2010 FBC-B TABLE 1609.7(2). |
| |
| 4) 2ND REQUEST. 2010 FBC 107.3.4.1 PRODUCT APPROVALS. |
| THOSE PRODUCTS WHICH ARE REGULATED BY THE DCA RULE |
| 9N-03 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| JURISDICTIONAL APPROVAL. |
| FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| SHOP DRAWINGS ETC.. |
| |
| 5) 2ND REQUEST. 2010 FBC-B 1609.1.2 PROTECTION OF |
| OPENINGS, 1609.6.4.41 COMPONENTS & CLADDING. FLORIDA |
| DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 |
| (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS |
| THAT WILL REQUIRE PRODUCT APPROVALS: |
| (31)(A) EXTERIOR DOORS. |
| (B) WINDOWS |
| (G) PRE-ENGINEERED A/C STANDS |
| |
| 6) COMPLIED. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| CONSTRUCTION SERVICES HOME PAGE |
| HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| |
| PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| |
| MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| |
| |