2013-02-25 11:12:03 | 701 SOUTH ROSEMARY AVENUE - SUITE #316 |
| PERMIT #13020210 |
| REVIEW COMMENTS - FIRE DEPARTMENT |
| |
| NO ADDRESS OR SUITE NUMBERS PROVIDED IN THE PLAN |
| TITLEBLOCK INFORMATION. |
| |
| UPDATE THE CODE LIST TO REFERENCE THE 2010 EDITION OF |
| THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE |
| 2009 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA |
| AMENDMENTS. |
| |
| ALL CONSTRUCTION AND DEMOLITION WORK SHALL CONFORM TO |
| THE REQUIREMENTS OF NFPA 241. SMOKING SHALL BE |
| PROHIBITED EXCEPT IN DESIGNATED EXTERIOR AREAS. ALL |
| OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL HAVE "NO |
| SMOKING" SIGNS POSTED. WHERE SMOKING IS PERMITTED, SAFE |
| RECEPTACLES FOR SMOKING MATERIALS SHALL BE PROVIDED. |
| |
| FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING |
| DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A |
| FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN |
| 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE |
| PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST |
| BE SUBMITTED IN WRITING (FAX: 561-804-4774) AND |
| APPROVED BY THE OFFICE OF THE FIRE MARSHAL LOCATED AT |
| 500 NORTH DIXIE HIGHWAY. |
| |
| PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY |
| RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING |
| NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM |
| WWW.KNOXBOX.COM. |
| |
| SHEET A-100: PLANS STATE THAT A CLEAR WIDTH OF 3'-0" |
| AND 3'-8" IS TO BE MAINTAINED FOR EXITING; PLEASE |
| INDICATE HOW THIS WILL BE ACCOMPLISHED AND MAINTAINED. |
| |
| SHEET A-800: THUMB-TURN STYLE DOOR LOCKS TO BE EQUIPPED |
| WITH A LOCK/UNLOCK INDICATOR. |
| |
| SHEET FP-210: PER FLORIDA ADMINISTRATIVE CODE SECTION |
| 61G15-32.004, FIRE PROTECTION ENGINEERING DOCUMENTS |
| SHALL INCLUDE THE POINT OF SERVICE FOR THE WATER |
| SUPPLY, A LIST OF APPLICABLE NFPA STANDARDS APPLICABLE |
| TO THE PROJECT, CLASSIFICATION OF HAZARD OCCUPANCY FOR |
| EACH ROOM OR AREA, SUPPRESSION SYSTEM TYPE, DESIGN |
| DENSITIES, WATER SUPPLY DATA (FIRE PUMP DATA, HYDRANT |
| FLOW TEST DATA) AND ANY PERFORMANCE BASED INFORMATION |
| SUCH AS PRE-ENGINEERED SYSTEMS. |
| |